Operation Manual
    <6. PARAMETERS>
6-5
IM 01F06A00-01EN
(4)  Item D : Additional Setup
These items are for Auxiliary Setup.
A value in “( )” is the data corresponding to the indicator.
Item Name R / W Data Range Unit
Decimal
Point
Remark
Initial
Value
Disp. U / D 
(*1)
D00 AUX. SETUP Menu D (Additinal Setup)
D10 LOW CUT W * to 32000 FU + C40 0 to 5 Low Cut Flow rate 
*Minimum Flow rate / 2
0.47 D
D20 TEMP UNIT W deg C 
deg F 
(0)
(1)
Selection of Temperature Unit (0) 
(*2)
DL
D21 TEMP f W -999.9 to 999.9 D20 1 Operating Temperature (Manual 
Setting Value)
15.0 
(*2)
DL
D25 DENSITY UNIT W kg/m
3
lb/cf 
lb/USgal 
lb/UKgal 
(0)
(1)
(2)
(3)
Selection of Density Unit (0) 
(*2)
DL
D26 DENSITY f W 0.00001 to 32000 D25 0 to 5 Operating Density (Manual Setting 
Value)
1024 
(*2)
DL
D30 OUT LIMIT (H) W 100.0 to 110.0 % 1 Upper Limit Value 110.0 D L
D35 BURN OUT R High 
Low 
(0)
(1)
Output Direction at Burn Out (0) D L
D40 SPECIAL UNIT No 
Yes 
Special 
(0)
(1)
(2)
Selection of change for Special Flow 
Unit
(0) D L
(Indicate and Set only for D40: Yes, Special)
D41 BASE UNIT R m
3
k m
3
l 
cf 
m cf 
k cf 
USgal 
kUSgal 
UKgal 
kUKgal 
bbl 
m bbl 
k bbl 
kg 
t 
lb 
k lb 
Nm
3
k Nm
3
M Nm
3
NI 
Sm
3
k Sm
3
M Sm
3
SI 
scf 
k scf 
M scf 
(0)
(1)
(2)
(3)
(4)
(5)
(6)
(7)
(8)
(9)
(10)
(11)
(12)
(13)
(14)
(15)
(16)
(17)
(18)
(19)
(20)
(21)
(22)
(23)
(24)
(25)
(26)
(27)
Basic unit for conversion to special 
unit
N: Normal
S: Standard
D
(Indicate and Set only for D40: Yes, Special)
D42 USER’S UNIT W 8 characters User’s unit 
(*3)
L
(Indicate and Set only for D40: Yes, Special)
D43 CONV 
FACTOR
 W 0.00001 to 32000 0 to 5 Conversion factor 1.0 D L
D60 SELF CHECK R GOOD 
ERROR
Self-diagnostic message
FU : Flow unit
(*1) : Available for 3.10 or greater version that can be checked in K50.
(*2) : If specifi ed when ordering, it is set to the specifi ed contents.
(*3) : Available characters are same as C10.
  Refer to Section 6.4 “Parameters Description.”