Operation Manual
    <14. EXPLOSION PROTECTED TYPE INSTRUMENT>
14-5
IM 01F06A00-01EN
14.2 FM
(1) Technical Data
• Explosion Proof
Applicable Standard: FM3600 2011, FM3611 2004, 
FM3615 2006, FM3810 1989, 
Including Supplement 1 1995, 
ANSI/NEMA 250 1991
Type of Protection: 
Explosionproof for Class I, Division 1, 
Groups A,B, C and D; 
 Dust-ignition proof for Class II/III, Division 1, 
Groups E, F,and G.
“SEAL ALL CONDUITS 18 INCHES.” 
“WHEN INSTALLED IN DIV.2, SEALS NOT 
REQUIRED”
Enclosure Rating: Type 4X 
Temperature Code: T6
Ambient Temperature: 
-29 to 60°C (Integral Type Vortex Flowmeter and 
Remote Type Vortex Flow Detector) 
 -40 to 60°C (Remote Type Vortex Flow 
Converter)
Power Supply: 42Vdc max. (Integral Type Vortex 
Flowmeter and Remote Type Vortex 
Flow Detector)
Output Signal (Integral Type Vortex Flowmeter): 
Current Output; 4 to 20mAdc 
Pulse Output; On=2Vdc, 200mA 
Off=42Vdc, 4mA
Output Signal (Remote Type Vortex Flow Detector): 
   Output Signal to Converter; 30Vp-p, 
100Ap-p
Input/Output Signal (Remote Type Vortex Flow 
Converter):   Current Output; 4 to 20mAdc 
Pulse Output; On=2Vdc, 200mA 
Off=42Vdc, 4mA
    Input Signal from Flowmeter; 
    30Vp-p, 100Ap-p
Electrical connection :  ANSI 1/2 NPT female (Special)
• Intrinsically Safe
Applicable Standard: FM3600 1998, FM3610 2010, 
FM3611 2004, FM3810 2005,
NEMA 250 1991, 
ANSI/ISA-60079-0: 2009, 
ANSI/ISA-60079-11: 2009
Type of Protection: 
Intrinsically safe for Class I, II, III, Div.1, Groups 
A, B, C, D, E, F and G,T4 and Class I, Zone 0, 
AEx ia IIC T4 Nonincendive for Class I, II, Div. 2, 
Groups A, B, C, D, F and G, Class III,Div.1, T4, 
and Class I, Zone 2, Group IIC, T4
Ambient Temperature: 
–29 to +60°C (Integral Type Vortex Flowmeter)
–29 to +80°C (Remote Type Vortex Flow 
Detector)
–40 to +60°C (Remote Type Vortex Flow 
Converter)
Indoors and Outdoors: Type 4X
Electrical Parameters: Vmax=30Vdc, 
Imax=165mAdc,
 Pi=0.9W, Ci=12nF, 
Li=0.15mH
Electrical connection : ANSI 1/2 NPT female
(2) Wiring
• Explosion proof 
WARNING
•  All wiring shall comply with National 
Electrical Code ANSI/NFPA 70 and Local 
Electrical Code.
•  “SEAL ALL CONDUITS 18 INCHES” 
“WHEN INSTALLED DIV.2, SEALS NOT 
REQUIRED”.
• Intrinsically Safe
NOTE
•  The FM Approved Hand Held Communicator 
may be connected at any point in the loop 
between the digitalYEWFLO and the Control 
Equipment.