Instruction Manual

10-11
IM DR231-01E
Basic Settings (SET-UP)
10
Setting Energizing/Deenergizing (ENERG)
This is a menu displayed for the /A4 option or /R1 option. The internal switches cannot be set.
Relay Setting
Set the object relays from one number relay (first relay) to another number relay (end relay).
Set it under the condition that the first relay number end relay number.
First relay number:
The first character is a unit number.
For the second and third characters, a number from 01 to 60 can be set but the effective
setting range is as shown in the following examples: (Check which slot the alarm module
or the DI/DO module is mounted in using its mounted position. Slot numbers are set in
the order of slot 0, slot 1, ..... as viewed facing the rear.)
Ex. 1: When the alarm module is mounted in slot 3: 31 to 40
Ex. 2: The DI/DO module is mounted in slot4: 41 to 42
End relay number: The same settings of the second or third characters in the first relay
number.
The default setting is 001-01.
Selection of energizing/deenergizing
ENERG: energizing
DE EN: deenergizing
The default setting is ENERG.
Setting Relay Hold (HOLD)
This is a menu displayed for the /A4 option or /R1 option. However, the internal switches are set
simultaneously with relays.
OFF: No relays/internal switches hold.
ON: all relays/internal switches hold.
The default setting is OFF.
Note
In order to make the set or selected contents effective, the contents must be registered. For details, see
page 10-24.
To return from the SET UP menu to the operation display mode, select END in the main menu. For
details, see page 10-24.
10.4 Setting Operation Mode of Relay/Internal Switch