Owner's manual

10-3
IM 04L31A01-01E
Computation and Report Function Related Operations
(Only on Models with the Computation Function Option)
10
Calculation expression
Set the equation (up to 40 characters) according to the description given on the
equation pop-up window. For a description on how to create equations, see
appendix
3, “Meaning and Syntax of Computing Equations.”
Span Lower/Upper
Set the upper and lower limits of the computation span (range of computed values).
Selectable range of values and the decimal place are as follows.
Selectable range of values: –9999999 to 99999999
Selectable decimal places: X.XXXX, XX.XXX, XXX.XX, XXXX.X
Unit
Enter the unit of the computed result using up to 6 alphanumeric characters.
Constant
Set the constants (K01 to K30) that are used in the equations. The number of
significant digits is 5 excluding the decimal point. When specifying the constant using
exponential notation, the mantissa is less than or equal to 5 digits, and the exponent
less than or equal to 2 digits.
The selectable range is as follows.
–9.9999E+29 to –1.0000E–30, 0, 1.0000E–30 to 9.9999E+29
Note
If the Math On/Off, calculation expression, or span setting is changed, the alarms for that
channel are turned [Off].
Setting Tags of Computation Channels
First-CH/Last-CH
You can assign channel numbers [31] to [60] as computation channels. The range of
numbers here is used to set the range of channels for setting the tag. The target
channels also apply to [Alarm delay], [TLOG], and [Rolling average] settings.
Tag
Enter the tag name using up to 16 alphanumeric characters.
Note
For the procedure in displaying tags in place of channel numbers, see
section 8.4,
“Measurement Function > Settings Related to Tag Display for Channels.”
10.1 Assigning Computation Channels and Setting Computing Equations, Constants and Tags