Owner's manual

5-13
IM 04L31A01-01E
Program Control Related Setup Operations
5
Setup Item
Event Output Settings
Pattern number (Version 3.02 or later)
Displayed when event output is set for each program pattern. Select a program
pattern number for which to set event output.
If this item is not displayed, the event output is common to all program patterns.
Event Types
Select whether to set event output for PV event or time event.
Relay Output
Turn the relay output ON or OFF.
Number
Select relay output terminal numbers from the following.
DO001-006, DO101-106, DO201-206, RO001-012 (only with the control DIO
expansion terminal block), SW001-SW036 (internal switches, style number S3 or
later)
Action
Displays the relay output action (energize/de-energize) per the settings.
Program Pattern End Signal Setting (Not Per Pattern, but Overall)
Relay Output
Turn the relay output ON or OFF.
Number
Select relay output terminal numbers from the following.
DO001-006, DO101-106, DO201-206, RO001-012 (only with the control DIO
expansion terminal block), SW001-SW036 (internal switch, style number S3 or later)
Action
Displays the relay output action (Energize/Deenergize) per the settings.
5.9 Event Output Settings