Setup Item
Logic Computation Settings
Setting Numbers
Up to 30 logic computations can be set. Select the numbers for the logic
computations.
Relay
Select the destination for the computed results.
DO001-DO006: Control output terminal block DO (for loops 1 and 2)
DO101-DO106: Control output terminal block DO (for loops 3 and 4)
DO201-DO206: Control output terminal block DO (for loops 5 and 6)
RO001-RO012: Control DIO expansion terminal block DO
SW001-SW036: Internal switches
Equation
Follow the instructions in the equation pop-up window to enter the equation (using
120 characters or less). The number of data that can be used in equations is 35. You
can also use the control constants W01-W36 in the equation. Measurement
constants K01-K36 cannot be used.
You can use the following operators.
Computation Type Operator
Logical operation AND, OR, XOR, NOT
Relational operation .GT., .LT., .GE., .LE., .EQ., .NE.
Conditional expressions [eq1?eq2:eq3]
See
appendix 3, “Meanings and Syntax of Equations”
for information on how to create
equations.
4.17 Logic Computation Settings (Style Number S3 or Later)