Ramp-rate time unit
Set the unit of time when setting a ramp grade per unit time to [Hour], [Minute], or
[Second].
SP ramp-down-rate/SP ramp-up-rate
Set this item to [On] (initial setting is Off) to decrease or increase the setpoint at a
constant rate of change, as opposed to a rapid change, when the SP is changed.
When set to [On], set the value that is to change per ramp-rate-time unit in the range
of “1 digit to EUS of measurement span (100%).”
Tag/Tag comment
Set the tag name or tag comment of each control loop using up to 8 alphanumeric
characters.
Setting Parameters Related to Zone PID
These settings are possible only when [Zone PID] under [Control] > [#1 Control action,
Input setting] is set to [On].
Loop number
The setup items of zone PID method are set for each loop. When changing these
parameters, this setting is used to select the target loop number [1] to [6] (initial value
is 1). The loop number is displayed up to the number of loops you specified at the
time of purchase.
Reference point
Set the reference points for the zone PID method.
The number of reference points that can be specified is “PID group number – 2.”
Reference points can only be specified when [PID number] is set to [3] or higher. For
a description on the settings of the number of PID groups, see
section 4.1, “Control >
Control action, Input setting.”
The selectable range of reference point values is shown using “EU (0.0 to 100.0%) of
the measurement span) in a pop-up window. Reference points set up to 100% are
valid. Set the reference points so that 1 2 3 4 5 6.
Switching hysteresis
Set the hysteresis used for switching zones at the reference points and deviation in
the range of “EUS (0.0 to 10.0%) of the measurement span” (initial value is 0.5%).
Can be specified when the [PID number] is set to 2 or greater.
Reference deviation
Set this value to [On] (initial value is Off) when selecting the PID value according to
the deviation from the SP (program setpoint). When set to [On], set the deviation in
the range of 1 digit to EUS (100.0%) of the measurement span.
Can be specified when the [PID number] is set to 2 or greater.