Owner's manual

4-22 IM 04L31A01-01E
Setup Items
Setting Control Alarms
Loop number
The setup items for control alarms are set for each loop. When changing these
parameters, this setting is used to select the target loop number [1] to [6] (initial value
is 1). The loop number is displayed up to the number of loops you specified at the
time of purchase.
Off/On
Up to four alarms can be registered per loop. Set only the alarms that are to be used to [On].
Type
Select the type of alarm from the following. Displayed symbols are indicated in parentheses.
PV high-limit alarm (PVH), PV low-limit alarm (PVL), deviation high-limit alarm (DVH),
deviation low-limit alarm (DVL), deviation high & low limit alarm (DVO), deviation
within high & low limits alarm (DVI), SP high-limit alarm (SPH), SP low-limit alarm
(SPL), output high-limit alarm (OTH), and output low-limit alarm (OTL).
Standby
This setting is valid when [Type] is set to [PV-High], [PV-Low], [Deviation-High],
[Deviation-Low], [Deviation-H&L], or [Dev-within-H&L]. Set whether to standby ([On]
or [Off]).
Relay Output/Number
Up to four alarms can be registered per control loop. For each alarm, turn ON/OFF
the relay output and select the contact output number when using relay output from
the list below. For example, [DO001] to [DO006] and [RO001] to [RO012] are
available selections of contact output numbers for the control alarm of loop 1.
DO001 to DO006: Loop 1 and 2 control output terminal block
DO101 to DO106: Loop 3 and 4 control output terminal block
DO201 to DO206: Loop 5 and 6 control output terminal block
RO001 to RO012: Control DIO expansion terminal block
SW001 to SW036: Internal switch (Style number S3 or later)
Note
The contact output is output from the terminal indicated as [DIGITAL OUT] on the label on the
back of the terminal cover. For the relationship between the contact output numbers and the
[DIGITAL OUT] terminals of each terminal block, see
page 2-6
.
Action
Indicates whether the relay output is energized or de-energized according to the
[Relay(Action/Behavior)] setting under [Control] > [Relay] (see
page 4-12
).
SP number/Alarm value
The control alarm outputs correspond to SP numbers [1] to [8]. Select the SP number
[1] to [8] and register alarm values for the four alarms of each SP number. The selectable
alarm values vary depending on the specified [Type] (alarm type) as follows:
PV high/low limits, SP high/low limits: EU of measurement span (0.0 to 100%)
Deviation high/low limits: EUS of measurement span (–100 to 100%)
Deviation high/low limits, within deviation high and low limits: EUS of measurement
span (0.0 to 100%)
Output value alarm: –5.0% to 105.0%
Clearing Alarms (AlarmACK)
If the [AlarmACK] operation is performed, all alarm indications and relay outputs are
cleared. However, this operation is invalid if the alarm indication/output relay behavior is
set to [Nonhold]. Alarms can be cleared using remote input (see
section 11.5, “Setting
the Measurement Remote Inputs”
) or via communications (see the
Communication
Interface User’s Manual
).
4.7 Control alarm