PVSwitching1 to 4 Selectable only during loop control with PV switching
Select to register a contact input for switching the input for each internal loop during
loop control with PV switching. This is not selectable for internal loops 5 and 6.
The rising edge signifies “PV2”; the falling edge signifies “PV1.”
Note
[PVSwitching1] or [PVSwitching2] does not appear as a selection, if the [Control mode] box
under [Control] > [#1 Control action, Input setting] is not set to [PVSwitching].
MemoryStart/Stop
Starts/stops the acquisition of the display data/event data to the internal memory
and the report function (computation option function). The rising edge of the signal
indicates start; the falling edge indicates stop.
If data acquisition is started, applying a rising signal produces no effect. Likewise,
if data acquisition is stopped, applying a falling signal produces no effect.
Trigger
Acts as an external trigger used to start the acquisition of event data to the internal
memory when in trigger mode or rotate mode. Input a signal for at least 250 ms.
AlarmACK
Clears the alarm indication and relay output. This is the same function as when the
[AlarmACK] soft key is pressed. Input a signal for at least 250 ms.
TimeAdjust
Adjusts the internal clock of the CX2000 to the nearest hour depending on the time
when the remote signal is applied. Input a signal for at least 250 ms.
Time the signal is input Time modification
00 min 00 s to 01 min to 59 s Truncates the minutes and seconds.
Example: 10 hours 01 min 50 s becomes 10 hours 00 min 00 s.
02 min 00 s to 57 min to 59 s The time is not changed.
58 min 00 s to 59 min to 59 s Rounds up the minutes and seconds.
Example: 10 hours 59 min 50 s becomes 11 hours 00 min 00 s.
MathStart/Stop
Starts/stops the computation. The rising edge of the signal indicates start; the
falling edge indicates stop. This is valid only on models with the computation
function option (/M1).
MathReset
Resets the data on all computation channels. Input a signal for at least 250 ms.
This is valid only on models with the computation function option (/M1) and while
the computation is stopped.
ManualSample
Write the instantaneous values of all channels to the internal memory once. Input
a signal for at least 250 ms. This excludes measurement channels set to skip and
computation channels set to Off.
Panel1Load to Panel3Load
Loads the setup data file named [LOAD1.PCL], [LOAD2.PCL], or [LOAD3.PCL]
stored on the external storage medium and activates the settings. Input a signal
for at least 250 ms. Setup data files named [LOAD1.PCL], [LOAD2.PCL], or
[LOAD3.PCL] must be created and saved to the external storage medium
beforehand.
Message1 to 8
Displays a message at the position corresponding to the time when the signal was
applied on the trend display. The displayed message is also written to the internal
memory. Input a signal for at least 250 ms.
4.2 Control > DI/DO/SW-registration/AUX (Alarm mode...)