Owner's manual

4-2 IM 04L31A01-01E
Setup Items
Setting Control Action Related Parameters
PID number
Set the maximum control parameter group number to be used in the range of [1] to [8]
(initial value is 8).
Control period
Select the control cycle from [250ms], [500ms], and [1s] (initial value is 250ms). However,
if basic setting mode > [#1 Alarm, A/D, Temperature] > [A/D Integrate] in basic setting
mode is set to [100ms], the control period is fixed to [1s] and is not selectable.
Zone PID
Set the PID selection method by turning [Off]/[On] the Zone PID.
Off (initial value): Target setpoint selection
If program control is ON on models with the program control option,
this becomes “segment PID.”
On: Zone PID
For the procedure in setting the reference point of the zone PID,
see
section 4.8, “Operation-related parameters/Zone PID.”
Restart mode
Select the action of the fixed-point control loop after recovering from an extended
power failure from [Continue], [Manual], [Auto] (initial value is Continue).
Continue: Continue the operation before the power failure occurred.
Manual: Start from a manual operation condition (control output is set to preset output).
Auto: Start from an auto operation condition (start the control output from preset
output and resume control computation based on the preset output).
Restart mode (Program) Only on models with the program control option
Select the restart mode (recovery behavior) the CX2000 will enter when recovering
from a power failure when program operation is performed. Select [Continue],
[Manual], or [Reset] (initial value is Continue).
Continue: Continue the operation before the power failure occurred.
Manual: Start from a manual operation condition (control output is set to preset output).
Reset: Start program operation from a reset condition (control output is set to
preset output).
Initial PID
Select [Temp] or [Press+Flow] (initial value is Temp) for the initial value of the PID
constant (see
page 4-24
). Below are the initial values of PID constants. The PID
constant is also initialized to the following value when [Initial PID] is changed.
Initial values for temperature: P = 5.0%, I = 240 s, and D = 60 s.
Initial values for pressure flow: P = 120.0%, I = 20 s, and D = 0 s.
6/4 loop select (set only on 6-loop models)
Select [6loop] or [4loop] (initial value is 6loop) for the number of loops used.
Auto tuning
Select [On] (initial value is Off) to enable the auto-tuning function of the PID constant.
Loop number
The [Control mode], [Program control], and [PID control mode] parameters are set for
each loop. When changing these parameters, this setting is used to select the target
loop number [1] to [6] (initial value is 1). The loop number is displayed up to the
number of loops you specified at the time of purchase.
Control mode
Select a control mode of [Single], [Cascade], [PVSwitching] (initial value is Single), or
[Retrans] (Style Number S3 or later). Select [Off] for the loops that are not to be controlled.
Different control modes (except for [Retrans]) cannot be specified on the two loops
within the single control output terminal block. If you specify [Cascade], both loops
are set to [Cascade]. You cannot select [Cascade] or [PVSwitching] for loop [5] or [6].
4.1 Control > Control action, Input setting