User guide

53
IM 04L31A01-02E
#7 Program control related (only when program control is ON)
<#1 Program parameter setting>
Parameter Selectable Range or Selections Initial Value
#1 Pattern initial setting
Program initial setting > Pattern number 1 to 4 (/PG1), 1 to 30 (/PG2) 1
Program initial setting > Segments 0 to 99 0
Program initial setting > Segment setting method Time, Ramp Time
Program initial setting > Pattern name Up to 16 alphanumeric characters Pattern 1
Program initial setting > Action loop > Loop 1 to 6 On/Off Off
#2 Wait action setting
Wait action setting > Wait zone 1 to 5 > Loop 1 to 6 On/Off Off
> High, Low EUS (100.0%) of the measurement span 1 digit
Wait action setting > Wait time 00:00:00 to 99:59:59 00:00:00
#3 Pattern start setting
Pattern start setting > Start target setpoint > Loop 1 to 6 EU (0% to 100%) of the measurement span –200.0
Pattern start setting > Start code StartTargetSP, RampPV1 to RampPV6, TimePV, StartTargetSP
#4 Program pattern setting
Program pattern setting > Segment number 1 to specified number of segments 1
Program pattern setting > Ramp/Soak select Ramp, Soak Ramp
Program pattern setting > Target setpoint > Loop 1 to 6 EU (0% to 100%) of the measurement span –200.0
Program pattern setting > Segment time
1
00:00:00 to 99:59:59 00:00:01
Program pattern setting > Ramp-rate time unit
2
Hour, Minute Hour
Program pattern setting > Ramp
2
1 digit to EUS (100.0%) of the measurement span 1 digit
Program pattern setting > Segment PID group No. 1 to specified PID number 1
Program pattern setting > Segment shift action Continue, HoldShift, LocalShift, ResetShift Continue
Program pattern setting > Wait action Off, Shift, Within Off
Program pattern setting > Wait zone number 1 to 5 1
#5 Event setting
Event setting > Segment number 1 to specified number of segments 1
Event setting > Event kind PVEvent, TimeEvent TimeEvent
Event setting > TimeEvent 1 to 16 On1, On2, On3, Off Off
Event setting > TimeEvent 1 to 16 > On-time, Off-time 00:00:00 to 99:59:59 00:00:00
Event setting > PVEvent 1 to 16 > Loop Off, 1 to 6 Off
Event setting > PVEvent 1 to 16 > Loop > Type PV-High, PV-Low, Deviation-High, Deviation-Low, Deviation-H&L, PV-High
Dev-within-H6L, SP-High, SP-Low, Output-High, Output-Low
Event setting > PVEvent 1 to 16 > Loop > Value PV: EU (0% to 100%) of the measurement span 1370.0
Deviation: EUS (0% to 100%) of the measurement span 1570.0
SP: EU (0% to 100%) of the measurement span 1370.0
Output: 5.0 % to 105.0 % 105.0 %
#6 Hysteresis (PV event)
Hysteresis (PV event) > PV event > Hysteresis 1 to 16 0.0% to 10.0 0.5%
#7 Repeat action setting
Repeat action setting > Repeat action Off, On, Repeat Off
Repeat action setting > On > Repeat frequency 1 to 999 1
Repeat action setting > Repeat action 1 to specified number of segments 1
> Repeat start segment
Repeat action setting > Repeat action 1 to specified number of segments 1
> Repeat end segment
1
When [Time] is specified for the segment setting method.
2
When [Ramp] is specified for the segment setting method.
<#2 Event output setting*>
Parameter Selectable Range or Selections Initial Value
Event output > Pattern number 1 to 4 (/PG1), 1 to 30 (/PG2) 1
Event output > Event kind PVEvent, TimeEvent TimeEvent
Event output > Relay Output EV1 to 16 On, Off Off
Event output > On EV1 to 16 > Number DO001 to DO006, DO101 to DO106, DO201 to DO206, DO001
RO001 to RO012, SW001 to SW036
Program pattern end signal > Relay Output On, Off Off
Program pattern end signal > On > Number DO001 to DO006, DO101 to DO106, DO201 to DO206, DO001
RO001 to RO012, SW001 to SW036
* With version 3.01, event output setting is included as item #6 within #1 Program pattern setting.
List of Parameters