User guide
51
IM 04L31A01-02E
Parameter Value or Selections Initial Value
#3 Tuning setting
Tuning setting > Loop number Ext1 to Ext16 Ext1
Tuning setting > 01 to 21 On/Off Off
Tuning setting > Item ID SP, A1, A2, A3, A4, P, I, D, OH, OL, MR, H, DR, ETC
DB, PO, or ETC
Tuning setting > Item name Up to 6 alphanumeric characters ETC
Tuning setting > Register address 30001 to 39999, 300001 to 365535, 40001
40001 to 49999, 400001 to 465535
Tuning setting > Decimal point 0 to 4 0
Tuning setting > Range lower –30000 to 30000, span width: 30000 0
Tuning setting > Range upper –30000 to 30000, span width: 30000 10
Setting mode (Control)
#1 Control input range
Parameter Selectable Range or Selections Initial Value
Input range > Loop number 1 to 6 1
Input range > Input type PV1, PV2, RemoteSP, or PVrange PV1
Input range > Mode TC, RTD, Scale, or 1-5V TC
Input range > Type DCV, TC, or RTD TC
Input range > Range TC: R/S/B/K/E/J/T/N//W/L/U/PLATI/PR/WRe K
RTD: PT/JPT PT
DCV: 20mV, 60mV, 200mV, 2V, 6V, 20V, or 50V 6 V
Input range > Span lower-limit Within the range of Range –200.0
Input range > Span upper-limit Within the range of Range 1370.0
Input range > PV range –30000 to 30000 Lower: 0.0, Upper: 2000.0
Input range > PV switching Lower limit –30000 to 30000 0.0
Input range > PV switching Upper limit –30000 to 30000 2000.0
Input range > Scale –30000 to 30000 Lower: 0.00, Upper: 200.00
Input range > Unit Up to 6 alphanumeric characters –
Input range > Square root On/Off Off
Input range > Low-cut 0.0% to 5.0% 1.0%
Input range > Bias On/Off Off
Selectable range when On: EUS (–100.0% to 100.0%) of 0.0%
the measurement span
Input range > Filter On/Off Off
1 s to 120 s 1 s
Input range > Ratio On/Off Off
Selectable range when On: 0.001 to 9.999 1.000
#2 Control alarm
Parameter Selectable Range or Selections Initial Value
Alarm > Loop number 1 to 6 1
Alarm > 1 to 4 On/Off Off
Alarm > Type PV-H (PV high-limit), PV-L (PV low-limit), PV-High
Dev-H (deviation high-limit), Dev-L (deviation low-limit),
Dev-H&L (deviation high & low limit),
D-W-H&L (deviation within high & low limits),
SP-H (SP high-limit), SP-L (SP low-limit),
Out-H (Output high-limit), or Out-L (Output low-limit)
Alarm > Standby On/Off Off
Alarm > Relay output On/Off Off
Alarm > Number DO001 to DO006, DO101 to DO106, DO201 to DO206, DO001, DO101, DO201
RO001 to RO012, or SW001 to SW036
Alarm > SP number 1 to 8 1
Alarm > Alarm value1 to 4 PV high/low limits: EU (0 to 100%) of measurement span, 1370.0
SP high/low limits: EU (0 to 100%) of measurement span,
Deviation high/low limits: EUS (–100 to 100%) of measurement span,
Deviation high & low limit and
deviation within high & low limits: EUS (0 to 100%) of measurement
span, or Output high/low limit: –5.0 to 105.0%
List of Parameters