User guide

49
IM 04L31A01-02E
Parameter Selectable Range or Selections Initial Value
AUX > Loop number 1 to 6 1
AUX > Remote setting Off or Remote Off
AUX > Alarm mode ALWAYS, STOP, or STOP/MAN ALWAYS
AUX > SP No. selection source 1 to 6 On/Off 1: On, 2-6: Off
AUX > PV/SP math On/Off Off
AUX > CLOG error Error, Skip Error
AUX > Event output setting Common/Separate Common
<#3 Output processing>
Parameter Selectable Range or Selections Initial Value
Output processing > Loop number 1 to 6 1
Output processing > Control output Relay, Voltage-pulse, Current-output, Current-output
or On/Off-control
Output processing > Cycle time 1 s to 1000 s 30 s
Output processing > Analog-output type 4-20 mA, 0-20 mA, 20-4 mA, or 20-0 mA 4-20 mA
<#4 Relay>
Parameter Selectable Range or Selections Initial Value
Relay > Module CTRL1-2, CTRL3-4, CTRL5-6, or EXTDIO CTRL1-2
Relay > FAIL On/Off Off
Relay > Self diagnosis On/Off Off
Relay > DO001 to 006 De_energize/Hold, De_energize/Nonhold, Energize/Nonhold
Energize/Hold, or Energize/Nonhold
Relay > RO001 to 012 De_energize/hold, De_energize/Nonhold, Energize/Nonhold
Energize/Hold, or Energize/Nonhold
<#5 Tuning setting>
Parameter Selectable Range or Selections Initial Value
Tuning setting > Loop number 1 to 6 1
Tuning setting > 01 to 21 On/Off 01-12: On, 13-21: Off
Tuning setting > 01 to 21 > Item ID SP, A1, A2, A3, A4, P,I, D, OH, OL, MR, 01: SP, 02: A1, 03: A2,
PO, H, DR, BS1, FL1, BS2, FL2, RT, RBS, 04: A3, 05: A4, 06: P,
RFL, or W01 to W36 07: I, 08: D, 09: OH,
10: OL, 11: MR,
12: PO, 13 - 21: SP
Tuning setting > 01 to 21 > Item name Up to 6 alphanumeric characters 01-12: same as Item ID,
13 - 21: –
<#6 External loop setting>
Parameter Value or Selections Initial Value
#1 Basic setting
Loop number Ext1 to Ext16 Ext1
Comm. Off/On On/Off Off
Modbus address 1 to 247 1
Connecting model UT320, UT321, UT350, UT351, UT420, UT450, UT520, UT550, UT320
UT750, or Others
Loop select First or Second First
Tag Up to 8 alphanumeric characters EXT-01
Tag comment Up to 8 alphanumeric characters
Auto reading Execute Execute
PV > Decimals 0 to 4 0
PV > Unit Up to 6 alphanumeric characters
SP > Decimals 0 to 4 0
SP > Unit Up to 6 alphanumeric characters
OUT > Decimals 0 to 4 0
OUT > Unit Up to 6 alphanumeric characters %
Control span lower –30000 to 30000, span width: 30000 0
Control span upper –30000 to 30000, span width: 30000 10
List of Parameters