User guide

48 IM 04L31A01-02E
<#6 Report E-Mail Settings>
Parameter Selectable Range or Selections Initial Value
Report E-Mail settings > Recipient1 On/Off Off
Report E-Mail settings > Recipient2 On/Off Off
Report E-Mail settings > Include source URL On/Off Off
Report E-Mail settings > Subject Up to 32 alphanumeric characters (CX) Report_data
Report E-Mail settings > Header1 Up to 64 alphanumeric characters
Report E-Mail settings > Header2 Up to 64 alphanumeric characters
#9 Aux, Time zone
Parameter Selectable Range or Selections Initial Value
AUX > Tag/Channel Tag/Channel Tag
AUX > Memory alarm Off, 1 h, 2 h, 5 h, 10 h, 20 h, 50 h, or 100 h 1 h
AUX > Language English, Japanese, German, French, or Chinese English
AUX > Partial Use/Not Not
Time zone > Difference from GMT –1200 to 1200 0
Batch Use/Not Use
#10 Control
<#1 Control action, Input setting>
Parameter Selectable Range or Selections Initial Value
Control action > PID number 1 to 8 8
Control action > Control period 250 ms, 500 ms, or 1 s
*
250 ms
Control action > Zone PID On/Off Off
Control action > Restart mode Continue, Manual, or Auto Continue
Control action > Restart mode (Program) Continue, Manual, or Reset Continue
Control action > Initial PID Temp or Press+Flow Temp
Control action > 6/4loop select 6 loop or 4 loop 6 loop
Control action > Auto tuning On/Off Off
Control action > Loop number 1 to 6 1
Control action > Control mode Off, Single, Cascade, PVSwitching, or Retrans Single
Control action > Control mode > Method Range, PVHigh, or Signal Range
Control action > Program control On/Off Off
Control action > PID control mode Follow-up or Fixed-point Follow-up
Input setting > Loop number 1 to 6 1
Input setting > Burnout > Measure1 Off, Up, or Down Up
Input setting > Burnout > Measure2 Off, Up, or Down Up
Input setting > Burnout > Remote Off, Up, or Down Up
Input setting > RJC > Measure1 External, Internal Internal
Input setting > RJC > Measure1 > Volt (uV) –20000 µV to 20000 µV0 µV
Input setting > RJC > Measure2 External, Internal Internal
Input setting > RJC > Measure2 > Volt (uV) –20000 µV to 20000 µV0 µV
Input setting > RJC > Remote External, Internal Internal
Input setting > RJC > Remote > Volt (uV) –20000 µV to 20000 µV0 µV
*
Fixed to 1 s for A/D integral time of 100 ms.
<#2 DI/DO/SW-registration/AUX (Alarm mode...)>
Parameter Selectable Range or Selections Initial Value
Contact input > Module CTRL1-DI, CTRL2-DI, CTRL3-DI, EXT1-RI, CTRL1-DI
CTRL1-DO, CTRL2-DO, CTRL3-DO, EXT1-RO,
INT-SW1, INT-SW2, INT-SW3
Contact input > DI001 to 006 None, AllControlStop, None
Contact input > DI101 to 106 AllControlStart, ControlStart/Stop (1 to 6),
Remote/Local (1 to 6), Auto/Man (1 to 6),
Contact input > RI001 to 012 Cascade (1-2 or 3-4), Auto1-2 or 3-4,
Contact input > DO001 to 006 Man1-2 or 3-4, SPNumber0 to 3 bit, ProgramRun,
Contact input > DO101 to 106 ProgramReset, Hold, Advance, PatternNo0 to 4bit,
Contact input > DO201 to 206 PVSwitching1 to 4, MemoryStart/Stop,
Contact input > RO001 to 012 Trigger, AlarmAck, TimeAdjust,
Contact input > SW001 to 036 MathStart/Stop, MathReset, ManualSample,
Panel1Load to Panel3Load, Message1 to 8,
Snapshot
List of Parameters