User guide
46 IM 04L31A01-02E
#7 Communication
<#1 Ethernet, Serial>
Parameter Selectable Range or Selections Initial Value
Ethernet > IP-address – 0.0.0.0
Ethernet > Subnet mask – 0.0.0.0
Ethernet > Default gateway – 0.0.0.0
Ethernet > DNS On/Off On/Off Off
Ethernet > Server search order > Primary – 0.0.0.0
Ethernet > Server search order > Secondary – 0.0.0.0
Ethernet > Host name Up to 64 alphanumeric characters –
Ethernet > Domain name Up to 64 alphanumeric characters –
Ethernet > Domain suffix search order > Primary Up to 64 alphanumeric characters –
Ethernet > Domain suffix search order > Secondary Up to 64 alphanumeric characters –
Serial > Baud rate 1200, 2400, 4800, 9600, 19200, or 38400 bps 9600 bps
Serial > Data length 7 or 8 8 bit
Serial > Parity Odd, Even, and None Even
Serial > RS-232 > Handshaking Off:Off, XON:XON, XON:RS, or CS:RS Off:Off
Serial > RS-422/485 > Address 1 to 32 1
Serial > RS-422/485 > Protocol Normal, Modbus, Modbus-M, or Ladder* Normal
Memory output Ethernet or serial Ethernet
*
Ladder is only on models with the ladder communication option
<#2 FTP client>
Parameter Selectable Range or Selections Initial Value
FTP transfer file > Disp&Event data On/Off Off
FTP transfer file > Report On/Off Off
FTP connection Primary or Secondary Primary
FTP connection > FTP server name Up to 64 alphanumeric characters –
FTP connection > Port number 1 to 65535 21
FTP connection > Login name Up to 32 alphanumeric characters –
FTP connection > Password Up to 32 alphanumeric characters –
FTP connection > Account Up to 32 alphanumeric characters –
FTP connection > PASV mode On/Off Off
FTP connection > Initial path Up to 64 alphanumeric characters –
<#3 Control (Login, Timeout)>
Parameter Selectable Range or Selections Initial Value
Ethernet login > Use/Not Use/Not Not
Ethernet login > Level admin, user1, user2, user3, user4, user5, admin
or user6
Ethernet login > Level > On/Off On/Off On
Ethernet login > Level > User name Up to 16 alphanumeric characters admin
Ethernet login > Level > Password Up to 6 alphanumeric characters 0
Application time out > On/Off On/Off Off
Application time out > Time 1 to 120 1 min
Keep alive > On/Off On/Off On
<#4 Modbus master>
Parameter Selectable Range or Selections Initial Value
Basic settings > Read cycle 125 ms, 250 ms, 500 ms, 1 s, 2 s, 5 s, 10 s, 15 s, 2 s
20s, or 30s
Basic settings > Timeout 125 ms, 250 ms, 500 ms, 1 s, 2 s, 5 s, 10 s, or 1 min 2 s
Basic settings > Retrials Off, 1, 2, 3, 4, 5, 10, or 20 1
Command settings > 1 to 8 On/Off Off
Command settings > 1 to 8 > Comm. Data First C01 to C30 C01
Command settings > 1 to 8 > Comm. Data Last C01 to C30 C01
Command settings > 1 to 8 > Address 1 to 247 1
Command settings > 1 to 8 > Salve Registers Input registers: 30001 to 39999, 300001 to 365535 30001
Hold registers: 40001 to 49999, 400001 to 465535
Command settings > 1 to 8 > Type INT16, UINT16, INT32_B, INT32_L, UINT32_B, INT16
UINT32_L, FLOAT_B, or FLOAT_L
List of Parameters