User guide
27
IM 04L31A01-02E
Displaying the Trend of PV, SP, and OUT Values
Below are the procedures for displaying the trends of PV, SP, and OUT of loop 1 on the
trend display of group number 1 (group name: GROUP 1).
1.
From the operation display, open the Group set, Trip line setting display according to
the following procedure.
Press the MENU key (to switch to Setting mode (Control)) and then the MENU key
(switch to Set mode). Press the #4 soft key (to select Display) and then the #1 soft
key (to select Group set, Trip line).
Menu (Setting mode (Control))
Menu (Setting mode)
Menu
2.
Press the arrow keys to move the cursor (blue) to the Channel setting box.
3.
Press the Input soft key to open the channel input pop-up window.
4.
Use the Character/Number key and soft keys to select the channels to include in
the group.
In this group setting, the PV, SP, and OUT of loop 1 are assigned channel numbers
101, 102, and 103, respectively. To include PV, SP, and OUT of loop 1, enter 101-
103 or 101.102.103.
Enter 101-103
Select 1
Channel input
pop-up window
5.
Press the DISP/ENTER key to confirm the entry.