User guide
14 IM 04L31A01-02E
Setting Control Alarms in Setting Mode
1.
From the operation display, click the MENU key to display the control setting menu.
2.
Press the #2 soft key (Control alarm).
3.
Press the arrow keys to move the cursor (blue) to the setup item box, press the soft
key of each value according to the following figure.
The numeric value of the alarm is entered using the pop-up window that appears by
pressing the Input soft key.
Select 1
Set to 600.0
Set to 800.0
Select DO002
Select DO001
Select On
Select PV-Low
Select PV-High
Select On
Select 1
4.
Press the DISP/ENTER key to confirm the settings.
Setting PID Parameters in Setting Mode
1.
From the operation display, click the MENU key to display the control setting menu.
2.
Press the #4 soft key (PID parameters).
3.
Press the arrow keys to move the cursor (blue) to the setup item box, press the soft
key of each value according to the following figure.
The numerical values such as the SP are entered using the pop-up window that
appears by pressing the Input soft key.
Select 1
Set to 700.0
Select Reverse
Select 1
Keep the initial PID
values for Temp
4.
Press the DISP/ENTER key to confirm the settings.
Examples of Control Setup Operation