Press the #1 soft key (Control action, Input setting).
3.
Press the arrow keys to move the cursor (blue) to the setup item box, press the soft
key of each value according to the following figure, and then press the DISP/ENTER
key.
Select 1
Select Single
(single loop)
Select Temp
(Set initial PID to P = 5%,
I = 240 s, and D = 60 s)
4.
Press the ESC key to return to the basic control setting menu.
5.
Press the #3 soft key (Output processing).
6.
Press the arrow keys to move the cursor (blue) to the setup item box, press the soft
key of each value according to the following figure, and then press the DISP/ENTER
key.
To set Cycle time, press the Input soft key to open a numeric entry pop-up window
as shown in the figure below. Enter the value using the Character/Number key and
the Space soft key and then press the DISP/ENTER key.
Select 1
Set to 3 s
Select Voltage-pulse
* No need to set
Analog-output type
Numeric entry pop-up
window
7.
Press the ESC key twice to return to the menu display (basic setting mode 2/2).
8.
Press the End soft key.
A confirmation window shown below opens.
9.
Press the DISP/ENTER key to confirm the settings.
Examples of Control Setup Operation