Temperature Unit, Time Zone, Time deviation limit, System Relay and Auxiliary
Functions
Click here (also selectable from [Setting] - [System Mode Setting]).
Temperature Unit
Selectthe°Cor°Fforthetemperatureunit.
GMT (Time Zone)
Set the time difference from the GMT.
Time deviation limit
If the time deviation between the specified time and the time on the DXP is within ±
(the value specified here) when data acquisition is in progress, the time on the DXP is
gradually corrected. Select [OFF], [10s], [20s], [30s], [1min], [2min], [3min], [4min], or
[5min].
If[Off]isselected,thetimecannotbeadjustedwhendataacquisitionisinprogress.
System Relay
Assign functions to the system relays 1 and 2.
FAIL: De-energized when failure occurs.
MEMORY END: Energized when the remaining write time of the internal memory is
less than or equal to the specified time, or when the free space of the external storage
medium is less than or equal to 10% or 6 MB.
BATCHSTART/STOP:EnergizedatMemoryStart,de-energizedatMemoryStop.
USERLOCKED:Therelayisenergizedwhenuserlockoccurs.
LOGIN: The relay is energized when there is a user logged into the DXP*.
* Login using keys and login to the setting function via the Ethernet or serial interface.
Aux
• Tag/Channel
Selectwhethertousethetagnameorchannelnumberasthemeasurement/
computation channel label.
• Memory Alarm Time
When the remaining time for storing the display or event data in the internal memory
fallstothespeciedtime(Memoryalarmtime),analarmisgeneratedviae-mailor
therelaycontactoutput(/F1option).
Memory Alarm: 1 h, 2 h, 5 h, 10 h, 20 h, 50 h, or 100 h
OFF: Do not use the memory end function.