Viewing and Creating Setup Data
2.6 Configuring the System Mode
Alarm/Relay/Remote
2. Click here (also selectable from [Setting] - [System Mode Setting]).
1. Select this tab.
Remote control
terminal number
Resets the range
selection.
Copy and paste the
selected range
(see page 4-15).
Select actions.
Alarm/Relay
Reflash
Whenmultiplealarmsaresettoonealarmoutputrelay,thisfunctionnotiesthe
succeedingalarmsaftertherstalarmthatcausestherelayactivation.
Relay AND
Settherangeofrelays(fromtherstalarmrelay)totaketheANDlogic.Allother
relays will be set to OR logic. If [NONE] is selected, all relays will operate using the
OR logic.
• AND:Activatedwhenallalarmsarebeinggeneratedsimultaneously.
• OR: Activatedwhenatleastoneofthealarmsisbeinggenerated.
Relay Action
Select whether to energize or de-energize the alarm output relay when the alarm
occurs.
Alarm Relay Behavior
• Unhold:TurnsOFFtheoutputrelaywhenthecauseofthealarmisnolongermet.
• Hold:HoldstheoutputrelayONuntilthealarmacknowledgeoperationisexecuted.
Alarm Indicator
Unhold, Hold: See “Alarm Relay Behavior.”
When [Alarm Relay Behavior] is set to [Hold], only [Hold] can be selected for the [Alarm
Indicator].
Rate of Change Increase/Rate of Change Decrease
Select the time interval for the rate of change alarms in terms of the number of
samplings (1 to 15).
Interval=scaninterval
×
number of samplings
Alarm Hysteresis
Awidth(hysteresis)of0.5%ofthedisplayspancanbespeciedonthevalueused
to set or release the alarm. This applies to upper (H) and lower (L) limit alarms on
measurement channels.