Viewing and Creating Setup Data
Input Type and Span
Mode, Range/Type
Select from the list of choices from the pull-down menu.
Input Type Mode Range/Type
DCVoltage VOLT 20mV,60mV,200mV,2V,6V,20V,50V
Thermocouple TC TypeR,S,B,E,K,J,T,N,W,L,U
Resistancetemperaturedetector RTD Pt100,JPt100,Cu10*,Cu25*
ON/OFFinput DI LEVEL(voltagelevel),CONT(Contact)
Measurement/DisplayOFF SKIP None
* /N1option
Note
IfSKIPisselected,settingssuchasDelta/Scale/SqrtandRange/Typearediscarded.
Span L, Span U
Sets the upper and lower limits (full scale) of the display.
When a value outside the range is entered or when the span L and span U values are set
to the same value, they are corrected when the data are checked.
Input value
Values within the
measurable range
Span L (0% on display)
Span U (100% on display)
Measured value
Difference Computation/Scaling/Square Root Computation
DELTA: Displays the difference between the input and the reference channel.
Note
Difference computation is performed between channels that have different [Mode] and
[Range/Type]settings.Thedecimalpositionofthecomputedresultissettothatofthe
channel computing the difference. If the number of digits to the right of the decimal of the
reference channel is greater than that of the channel computing the difference, the reference
value below the least significant digit of the channel computing difference is rounded
beforehand.
SCALE:Convertstheinputvaluetoavalueintheappropriateunit.
SQRT:Computesthesquarerootoftheinput.Theresultisconvertedtoavalueinthe
appropriateunit.ThissettingcanbeusedonlywhentheinputmodissettoVOLT.
Input value
Measured value on the reference channel
DELTA
SCALE
SQRT
Input value
+
Span L Scale L
Decimal position
Unit
Decimal position
Unit
Span U
Scale
conversion
Scale U
Input value
Span L
Span U
Span L Scale L
Span U
Scale
conversion
Scale U
Measured value Measured value
Measured value
–
Span L, Span U
Sets the appropriate upper and lower limits (see figures above).
When a value outside the range is entered or when the span L and span U values are set
to the same value, they are corrected when the data are checked.
2.3 Setting the Measurement Channels