User guide

3-31
M-4659
Configuring the DX1000/DX2000
1
2
3
4
5
6
7
8
Index
• Comm. Security
Settings Description
Login Enables only registered users to operate the DX via communications. The
[User registration] is displayed in the basic setting mode menu.
OFF Disables the security functions.
• Auto Save
Settings Description
ON Automatically saves the measured data to the CF card.
OFF Does not automatically save the data. Save the measured data manually to
the CF card or USB flash memory (/USB1 option).
• Media FIFO
You can select this with DX main unit firmware version 2.0x or later.
This is valid only when [Auto Save] is [ON].
Settings Description
ON If there is no more free space on the CF card, the oldest file is deleted, and
the newest file is saved.
OFF If there is no more free space on the CF card, the measured data is not saved
to the CF card.
Option
• Value on Error
Specify whether to set the display for a computation error to [+Over] or [–Over].
• Overflow Sum, Ave
Specify how to handle overow data when it is detected in the SUM or AVE
computation of TLOG or CLOG. This setting is also applied to report generation.
Settings Description
Error Sets the computed result to computation error.
Skip Discards the overflow data and continues the computation.
Limit Uses a limit value in place of the overflow data and continues the
computation.
• OverflowMin,Max,P-P
Specify how to handle overow data when it is detected in the MAX, MIN, or P-P
computation of TLOG or CLOG. This setting is also applied to report generation.
Settings Description
Over Uses the overflow data as-is.
Skip Discards the overflow data and continues the computation.
• Report (1 to 4)
Select the type of data to output as reports.
Settings Description
OFF Does not output reports. You cannot set Report 1 to [OFF].
Ave Outputs the average value.
Max Outputs the maximum value.
Min Outputs the minimum value.
Sum Outputs the sum value.
Instant Outputs the instantaneous value.
3.6 Entering Basic Settings