User guide
3-25
M-4659
Configuring the DX1000/DX2000
1
2
3
4
5
6
7
8
Index
Event Action
Event Action No.
You can set up to 40.
Event
The condition to execute the action.
Settings Description
NONE Not use.
Remote Select the remote control input terminal number.
Relay Select the alarm output relay number.
Switch Select the internal switch number.
Timer Select the timer number.
Match Time Select the match timer number.
Alarm -
User Key -
Action
The action to be executed when an event occurs.
Settings Description
Memory Start/Stop -
Memory Start -
Memory Stop -
Trigger Can be specified when the DX is configured to record event data.
AlarmACK Cannot be specified when the event is set to [Relay], [Switch], or
[Alarm].
Math Start/Stop Can be specified on /M1 and /PM1 options.
MathStart Can be specified on /M1 and /PM1 options.
MathStop Can be specified on /M1 and /PM1 options.
Math Reset Can be specified on /M1 and /PM1 options.
Save Display Data Can be specified when the DX is configured to record display data.
Save Event Data Can be specified when the DX is configured to record event data.
Message Set the message number and the destination. Set the message
destination to all groups (All) or a group number.
Snapshot -
Display Update
Interval Change
Can be specified when the function for switching between the trend
update interval and the secondary update interval is enabled.
Manual Sample -
Timer Reset Cannot be specified when the event is set to [Timer].
Display Group
Change
Specify the number of the group to be displayed.
Flag Can be specified on /M1 and /PM1 options.
Time ADJUST Can be specified only when the event is set to [Remote].
Panel Load Can be specified only when the event is set to [Remote].
3.5 Entering General Settings