User guide

7-28
M-4659
DIO Operation Monitoring Function (CX Style Number S3 or Later)
DIO Operation Monitoring Number
Enter an integer between 1 and 36.
DIO Operation Monitoring Function
Turns the specified DIO operation monitor number ON and OFF.
DIO Types
Select the DIO operation monitoring method.
DI-1: Displays the input status of the specied DI. The status of the internal
switches are output.
DO-1: The status of the internal switches are output to one DO. 1 (ON) is output
when the internal switches are ON, and 0 (OFF) is output when they are
OFF.
DO-2: You can output the ON and OFF statuses of the internal switches to
separate DOs. 1 (ON) is output from the ON output DO when the internal
switches are ON, and 0 (OFF) is output from the OFF output DO when
they are OFF. 0 (OFF) is output from the ON output DO when the internal
switches are OFF, and 1 (ON) is output from the OFF output DO when they
are ON.
DIO-11: The same action as the DO-1 is performed while displaying the input status
of the specied DI.
DIO-12: The same action as the DO-2 is performed while displaying the input status
of the specied DI.
DO-2P: You can output the ON and OFF statuses of the internal switches to
separate DOs. A pulse signal having a 1 to 2 second pulse width is output
from the ON output DO when the internal switches are ON, and from the 0
(OFF) output DO when they are OFF.
DOI-12P: The same action as the DO-2P is performed while displaying the input
status of the specied DI.
SWNumber
Set the internal switches assigned to DO.
DO Number
Set the DO performing DIO operation monitoring. If the DIO type is DO-2, DIO-12, DO-
2P, or DIO-12P, specify a separate DO with ON and OFF. DO numbers may not overlap
with other numbers, including DIO operation monitoring numbers.
Not displayed when the DIO type is DI-1.
7.4 Control Function General Settings