Instruction Manual
6-48 IM 04L31A01-17E
Example Send report generation notification e-mail
messages including the source URL to recipient
1. The subject is “Report”, and the header is
“LP2”.
YUREPORT,ON,OFF,ON,Report,LP2
Description • For the contents of the system notification,
see section 2.11.
• Report generation notification can be used on
models with the computation function option /
M1.
• For details on the settings of e-mail, see
sections 2.3 and 2.11.
YV Sets the e-mail recipient address
Syntax YV p1,p2<terminator>
p1: Select Recipient
1: Recipient 1
2: Recipient 2
p2: Recipient address (up to 150 characters)
Query YV[p1]?
Example Set recipient 1 to “Cont@good.com” and
“Adm@good.com”.
YV1,Cont@good.com Adm@good.com
Description • To set multiple recipients, separate each
recipient with a space.
• For details on the settings of e-mail, see
sections 2.3 and 2.11.
YW Sets the e-mail sender address
Syntax YW p1<terminator>
p1: Sender address (up to 64 characters)
Query YW?
Example Set the sender address to “CX2000”.
YWCX2000
Description For details on the settings of e-mail, see sections
2.3 and 2.11.
YX Sets the e-mail SMTP server
name
Syntax YX p1,p2<terminator>
p1: SMTP server name (up to 64 characters)
p2: Port number (0 to 65535).
Query YX?
Example Set the SMTP server to “mhs.good.com” and
port number to “25”.
YXmhs.good.com,25
Description For details on the settings of e-mail, see sections
2.3 and 2.11.
6.7 Basic Setting Commands (Measurement)
ML Sets the communication buffer
recovery processing
Syntax ML p1<terminator>
p1: DO/internal switches processing
Continue: hold the status
Clear: clear the status
Query ML?
Example During communication buffer recovery, clears
DO and the internal switches.
MLclear
MM Sets the modbus mouse/
temperature meter
communication automatic
recovery
Syntax MM p1,p2<terminator>
p1: Turns automatic recovery On/Off
p2: Intervals: 1min, 2min, 5min, 10min, 20min,
30min, or 60min.
Query MM?
Example Temperature meter communications
automatically restored after 5 minutes.
MMON,5min