Instruction Manual

6-42 IM 04L31A01-17E
6.7 Basic Setting Commands (Measurement)
XR Sets the remote action
Syntax XR p1,p2<terminator>
p1: Remote number (1 to 8)
p2: Remote action
NONE No action
ALARM ACK Alarm acknowledge
MEMORY START/STOP
Start/stop measurement
MANUAL SAMPLE
Manual sample
TRIGGER External trigger input
(event data)
MESSAGE1 Write message 1
MESSAGE2 Write message 2
MESSAGE3 Write message 3
MESSAGE4 Write message 4
MESSAGE5 Write message 5
MESSAGE6 Write message 6
MESSAGE7 Write message 7
MESSAGE8 Write message 8
PANEL1 LOAD Load setting 1
PANEL2 LOAD Load setting 2
PANEL3 LOAD Load setting 3
MATH START/STOP
Start/Stop MATH
MATH RESET Reset MATH
TIME ADJUST Adjust time
SNAPSHOT Snapshot
Query XR[ p1]?
Example Set the remote action of remote number 1 to
writing message 1.
XR1,MESSAGE1
XQ Sets the timer
When not using the timer
Syntax XQ p1,p2<terminator>
p1: Timer number (1 to 3)
p2: Timer type (OFF)
Query XQ[ p1]?
Example Turn the number 1 timer OFF.
XQ1,OFF
Description This command can be used on models with the
computation function option /M1.
When using the absolute timer
Syntax XQ p1,p2,p3,p4,p5,p6<terminator>
p1: Timer number (1 to 3)
p2: Timer type (ABSOLUTE)
p3: Interval (1MIN, 2MIN, 3MIN, 4MIN, 5MIN,
6MIN, 10MIN, 12MIN, 15MIN, 20MIN,
30MIN, 1H, 2H, 3H, 4H, 6H, 8H, 12H, 24H)
p4: Reference Time (hh fixed form)
hhHour (00 to 23)
p5: Reset/not reset the sum value when the
timer expires. (ON/OFF)
p6: Action to be taken when the timer expires
(OFF, DATA SAVE)
Query XQ[ p1]?
Example Set an absolute timer to timer number 1. Set the
sampling interval to 30 minutes, the reference
time to 7 O’clock, reset the integrated value
when the timer expires, and set no action when
the timer expires.
XQ1,ABSOLUTE,30MIN,07,ON,OFF
Description This command can be used on models with
the computation function option /M1.
The timer expires at the interval specified by
parameter 3 from the time specified by p4,
and performs the operation set with
parameters p5 and p6.
When using the relative timer
Syntax XQ p1,p2,p3,p4,p5<terminator>
p1: Timer number (1 to 3)
p2: Timer type (RELATIVE)
p3: Interval (hh:mm fixed format)
hh Hour (00 to 24)
mm Minute (00 to 59)
Set the interval in the range 00:01 to 24:00
p4: Reset/not reset the sum value when the
timer expires. (ON/OFF)
p5: Action to be taken when the timer expires
(OFF, DATA SAVE)
Query XQ[ p1]?
Example Set a relative timer to timer number 1. Set the
sampling interval to 1 hour 15 minutes, reset the
integrated value when the timer expires, and set
no action when the timer expires.
XQ1,RELATIVE,01:15,ON,OFF
Description This command can be used on models with
the computation function option /M1.
The timer expires at the interval specified by
parameter p3 from the time the CX is turned
ON, from the time the timer is reset, and from
the time when the timer is turned OFF. When
the timer expires, the operation set with
parameters p4 and p5 are carried out.
RO Sets the report type and
generation time
When report type is set to none
Syntax RO p1<terminator>
p1: Report type (OFF)
Query RO?
Example Set report to none.
ROOFF
Description This command can be used on models with the
computation function option /M1.