Instruction Manual

6-39
IM 04L31A01-17E
6
Command
LI Saves the setup data
Syntax LI p1<terminator>
p1: File name (up to 8 characters)
Example Save the setup data of both setting and basic
setting commands to the file SETFILE2.
LISETFILE2
Description A “.pcl” extension is attached to the saved file.
This command cannot be specified on models
that do not have an external storage device or
when a medium is not inserted into the drive.
This command cannot be used while the
setup data file is being output (specified using
the FE command).
This command cannot be used when the #1
Program parameter setting display under #7
Program-control parameters in Set mode is
shown(or after sending the PB command).
CM Sets the communication input
data
Syntax CM p1,p2<terminator>
p1: Communication input data number (C01 to
C30)
p2: Communication input data
The selectable range is –9.9999E+29 to –
1.0000E–30, 0, and 1.0000E–30 to
9.9999E+29
(The + sign of “E+” can be omitted.)
Query CM?
Example Set 1.0000E–10 to communication input data
number C01.
CMC01,1.0000E-10
Description This command can be used on models with the
computation function option /M1.
EM Starts/stops e-mail transmission
function
Syntax EM p1<terminator>
p1: Operation type
0 Start
1 Stop
Example Start the e-mail transmission function.
EM0
Description To use the e-mail transmission function, you
must set the Ethernet interface, e-mail address,
and contents to be transmitted. For details on
setting these items, see section 2.11.
DL Mode switching for the DIO
operation monitoring function
Syntax DL p1,p2<terminator>
p1: DIO operation monitoring number (01–36,
1–12 for the CX1000)
p2: Auto/manual switching
0 Automatic
1 Manual
Example When the output mode for DIO operation
monitoring number 4 is Automatic.
DL4,0
DM Sets the manual output value for
DIO operation monitoring
function
Syntax DM p1,p2<terminator>
p1: DIO operation monitoring number (01–36,
1–12 for the CX1000)
p2: Manual output value
0 Off
1On
Example Set DIO operation monitoring number 4 to
Manual.
DM4,1
DP DO/internal switch status
settings
Syntax DP p1,p2<terminator>
p1: Relay numbers
DO001-DO006
DO101-DO106
DO201-DO206
RO001–RO012 (expansion module)
SW001–SW036 (internal switch)
DO001-DO006 and SW001-SW018 for the
CX1000.
p2: Status of relay (switch)
0 Off
1On
Example Turn internal switches SW008 ON.
DPSW008,1
6.6 Setting Commands (Operation)