Instruction Manual

6-26 IM 04L31A01-17E
External Loop PID Parameter Settings
DT Sets the external loop PID
parameter
Syntax DT p1,p2,p3,p4<terminator>
p1: Loop number (1–16, or 1–4 on the CX1000)
p2: Loop number
1–4 for UT320/UT321/UT350/UT351
1–8 for UT420/UT450/UT520/UT550/UT750
p3: PID parameter name
SP: target setpoint (EU(0.0–100.0%)
A1-A4: Alarm 1–4 setting value (or alarm
1–3 for the UT320/UT321/UT350/
UT351/UT420)
Measured value alarm/setting
value alarm: measured input
range of -100.0–100.0%
Deviation alarm: measured input
range span of -100.0–100.0%
Output value alarm: -5.0–105.0%
Time alarm (alarm 1 only): -1–
5999
P: Proportional band setting (1–9999)
OH: Output limit upper limit value (-5.0–
105.0%)
OL: Output limit lower limit value (-5.0–
105.0%)
MR: Manual reset (-5.0–105.0%)
(Active when integral time I is OFF)
H: On/off control hysteresis
During On/off control: Measured input
range span of -100.0–100.0%
During position proportional PID
control: 0.0-100.0%
DB: Dead band
During position proportional PID
control: 1.0-10.0%
DR: Correct back switching operation [2]
0: Back, 1: Right action [2]
PO: Preset output value (-5.0–105.0%)
For loops set to the CX’s external loop
tuning item, the external loop tuning
items take precedence.
p4: Parameter value
Measured value varies depending on p3’s
PID parameter.
Query DT[ p1,p2 (,p3)]?
Example Set external loop 1, group number 1, and PID
parameter SP to 1000.
DT1,1,SP,1000
Description The parameter setting range differs depending
on the UT used.
p4 is not needed for the UT320, UT321,
UT350, UT351, and UT420.
Integral time/derivative time settings
Syntax DT p1,p2,p3,p4,p5<terminator>
p1: Loop number (1–16, or 1–4 on the CX1000)
p2: Loop number
1–4 for UT320/UT321/UT350/UT351
1–8 for UT420/UT450/UT520/UT550/UT750
p3: PID parameter name
I: Integral time
D: Derivative time
p4: Turns integration/differentiation On/Off
p5: Parameters when p4 is ON (1–6000)
Query DT[ p1,p2 (,p3)]?
Example Set external loop 2, group number 2, and PID
parameter D to 2000.
DT2,2,D,ON,2000
Description Given the query, DT p1, p2?, returns the PID
parameter for p2's group number and the
setting values of each parameter.
The PID parameters that can be set vary
depending on the control mode of the external
groups, and the control output type.
On/off control:
SP, A1-A4, H, DR, PO
Other than On/off control
SP, A1-A4, P, I, D, OH, OL, MR, DR, PO
Position proportional control
SP, A1-A4, H, P, I, D, OH, OL, MR, DR, DB,
PO
Internal switches primary
SP, A1-A4, P, I, D, OH, OL, MR, DR
External Loop Control Parameter Settings
DV External loop control parameter
settings
Syntax DV p1,p2,p3<terminator>
p1: Loop number (1–16, or 1–4 on the CX1000)
p2: Parameter names
MODE/AT/RL/SR/MOUT/SPN
p3: Parameter value
MODE: Switch between manual/automatic/
cascade
0: Automatic operation
1: Manual operation (cascade
control’s primary loop cannot be
selected)
2: Cascade operation (only
cascade control’s secondary
loop can be selected)
AT: Execution and stop of auto tuning
0: Stop auto tuning
1: Execute PID number 1
:
8: Execute PID number 8
9: ALL
For UT320/UT321/UT350/ UT351,
5–8 is not needed.
6.5 Setting Commands (Measurement)