Instruction Manual
6-21
IM 04L31A01-17E
6
Command
PT Sets the segment time
Syntax PT p1,p2<terminator>
p1: Segment number (1 to 99)
p2: Segment time (hh:mm:ss fixed format)
hh Hour (00 to 99)
mm Minute (00 to 59)
ss Second (00 to 59)
Set a value greater than or equal to 1 s.
Query PT[ p1]?
PU Sets the ramp-rate time unit/
ramp
Syntax PU p1,p2,p3<terminator>
p1: Segment number (1 to 99)
p2: Ramp-rate time unit (Hour, Minute)
p3: Ramp (ramp per unit time 1 digit to EUS
(100%))
Query PU[ p1]?
PG Segment PID group number
Syntax PJ p1,p2<terminator>
p1: Segment number (1 to 99)
p2: Segment PID group number (1 to 8)
Query PG[ p1]?
PJ Sets the segment shifting action
and wait
Syntax PJ p1,p2,p3,p4<terminator>
p1: Segment number (1 to 99)
p2: Segment shifting action*
p3: Wait (Off/Shift/Within)
p4: Wait zone number (1 to 5) (selectable only
when p3 is set to Shift or Within)
*:Continue/HoldShift/LocalShift/
ResetShift
Query PJ[ p1]?
Event Setting
ET Sets the time event
Syntax ET p1,p2,p3,p4,p5<terminator>
p1: Segment number (1 to 99)
p2: Event number (1 to 16)
p3: Enable/disable event (Off, On1, On2, On3)
p4: On-time (hh:mm:ss fixed format)
hh Hour (00 to 99)
mm Minute (00 to 59)
ss Second (00 to 59)
p5: Off-time (hh:mm:ss fixed format)
hh Hour (00 to 99)
mm Minute (00 to 59)
ss Second (00 to 59)
P5>P4
Query ET[ p1,p3]?
6.4 Setting Commands (Control)
Wait Action Setting
PZ Sets the wait zone
Syntax PZ p1,p2,p3,p4,p5<terminator>
p1: Loop number (1 to 6) (1 or 2 on the CX1000)
p2: Wait zone number (1 to 5)
p3: Wait Off/On
p4: High boundary of the zone (1 digit to EUS
(100.0%))
p5: Low boundary of the zone (1 digit to EUS
(100.0%))
p4 and p5 can be specifed only when p3 is ON.
Query PZ[ p1,p2]?
PW Sets the wait time
Syntax PW p1,p2<terminator>
p1: Wait zone number (1 to 5).
p2: Wait-time setting (hh:mm:ss fixed format)
hh Hour (00 to 99)
mm Minute (00 to 59)
ss Second (00 to 59)
Query PW[ p1]?
Program Initial Setting
PO Sets the start setpoint
Syntax PO p1,p2<terminator>
p1: Loop number (1 to 6) (1 or 2 on the CX1000)
p2: Start target setpoint EU (0.0 to 100.0%)
Query PO[ p1]?
PQ Sets the start code
Syntax PQ p1<terminator>
p1: Start code*
*: StartTargetSP
RampPV1Start
TimePVStart
RampPV2Start
RampPV3Start
RampPV4Start
RampPV5Start
RampPV6Start
Query PQ?
Program Operation Parameters
PD Sets the ramp/soak select
Syntax PD p1,p2<terminator>
p1: Segment number (1 to 99)
p2: Ramp/soak selection (Ramp/Soak)
Query PD[ p1]?
PM Sets the final target setpoint
Syntax PM p1,p2,p3<terminator>
p1: Segment number (1 to 99)
p2: Loop number (1 to 6) (1 or 2 on the CX1000)
p3: Final target setpoint EU (0.0 to 100.0%)
Query PM[ p1,p2]?