Instruction Manual

6-20 IM 04L31A01-17E
When PV/SP Computation Function is ON
Syntax HE p1,p2,p3,p4<terminator>
p1: Control input channel numbers (CI01–CI10,
or CI01–CI05 for the CX1000)
p2: Ten segment linearizer number (1–11)
p3: Ten segment linearizer input
Ten segment linearizer approximation
EU(-5.0-105.0%)
Ten segment linearizer bias
EU(-5.0-105.0%)
p4: Ten segment linearizer output
Ten segment linearizer approximation
EU(-5.0-105.0%)
Ten segment linearizer bias
EUS(-100.0-100.0%)
Query HE[ p1,p2]?
Example Set the CI01 (whose input type is set to RTD
type JPT and ten-segment linearizer mode set to
ten-segment linearizer bias) as follows: ten-
segment linearizer input of segment number 2:
500.0, output: maximum value in the selectable
range.
HECI01,2,5000,7750
Pattern Initial Setting
PB Sets initial pattern
Syntax PB p1,p2,p3,p4,p5,p6<terminator>
p1: Pattern number (1 to 30)
p2: Used segments (0 to 99). However, the
total number of segments used in all
patterns must be 300 or less.
p3: Segment setting method (Time, Ramp)
p4: Pattern name (up to 16 alphanumeric
characters.)
p5: Edit segment (Off/Delete/Insert)
Can be specified only when P2 is not 0.
p6: Edit segment number (1 to 99). However,
within the number of used segments. Can
be specified only when p5 is not off.
Query PB[ p1]?
Description When program control is in execution, p1 and
p2 are pattern number and pattern name,
respectively. Other parameters cannot be set.
When the setup data file is being output
(specified using the FE command), this
command cannot be used.
PI Operating loop designation
Syntax PI p1,p2<terminator>
p1: Loop number (1–6, or 2 on the CX1000)
p2: Operation designation (On/Off)
Query PI[ p1]?
6.4 Setting Commands (Control)
Ten-segment Linearizer Input/Output
HA Sets the ten-segment linearizer
mode
When the PV/SP Computation Function is OFF
Syntax HA p1,p2,p3<terminator>
p1: Loop number (1 to 6) (1 or 2 on the CX1000)
p2: Input type (PV1, PV2)
p3: Ten-segment linearizer mode (Off, Biasing,
and Approximation)
Query HA[ p1,p2]?
Example Set the ten-segment linearizer mode of loop 6
PV1 to ten-segment linearizer bias.
HA6,PV1,BIASING
When the PV/SP Computation Function Is ON
Syntax HA p1,p2<terminator>
p1: Control input channel numbers (CI01–CI10,
or CI01–CI05 for the CX1000)
p2: Ten segment linearizer mode (Off, Biasing,
and Approximation)
Query HA[ p1]?
Example The ten segment linearizer mode of CI01 is set
to ten segment linearizer bias.
HACI01,BIASING
HE Sets the ten-segment linearizer
segment
When the PV/SP Computation Function is OFF
Syntax HE p1,p2,p3,p4,p5<terminator>
p1: Loop number (1 to 6) (1 or 2 on the CX1000)
p2: Input type (PV1, PV2)
p3: Segment number (1 to 11)
p4: Ten-segment linearizer input
Ten-segment linearizer approximation
EU(–5.0 to 105.0%)
Ten-segment linearizer bias
EU(–5.0 to 105.0%)
p5: Ten-segment linearizer output
Ten-segment linearizer approximation
EU(–5.0 to 105.0%)
Ten-segment linearizer bias
EUS (–100.0 to 100.0%)
Query HE[ p1,p2,p3]?
Example Set the PV1 of loop 1 (whose input type is set to
RTD type JPT and ten-segment linearizer mode
set to ten-segment linearizer bias) as follows:
ten-segment linearizer input of segment number
2: 500.0, output: maximum value in the
selectable range.
HE1,PV1,2,5000,875