Owner's manual
3-6
IM WX1-05E
Group Names
You can assign names to groups. Names can contain up to 30 alphanumeric characters.  
The group names specified here are the default values when Remote Monitor is 
connected to GateMODBUS. 
Acquiring Data at Fixed Intervals
Using GateMODBUS, data can be acquired concurrently on each port. Therefore 
data is logged more efficiently when connecting each Modbus device to a separate 
port rather than connecting several Modbus devices to a single port. Also, registers 
occurring in a continuous sequence on 1 instrument are read all at once. Therefore, the 
more sequentially continuous registers there are, the more efficiently data is acquired. 
However, if a register within the sequence experiences an error, the error applies to all 
registers in the sequence. 
For example, given the three registers below, TAG001–TAG003 are read all at once at 
each scan interval. 
Tag COM Port Modbus Address Register numbers read
TAG001 COM1 1 30001
TAG002 COM1 1 30002
TAG003 COM1 1 30003
Data Dropout
If data is being read at the timing shown below, data is dropped. Data dropout can occur 
in the following circumstances. 
•  If the time requ
ired to read the tags is longer than the scan interval
  In the gure below, by the time the tags at T1 have been read, T2 has already passed 
and T3 begins. Therefore, the tags to have been read at T2 were dropped.
TAG001 TAG002 TAG003 TAG004 TAG001 TAG002 TAG003 TAG004
T T1 = T + ∆t T2 = T + ∆t x 2 T3 = T + ∆t x 3
Interval: ∆T
Data reading at time T
Data reading at time T1
Time
Data
dropout
occurs
Time
Timing of Data Reading
3.2 Detailed Description of Functions