Owner's manual

3-4
IM WX1-05E
Logical Configuration
Item Description Limit
Tag Indicates one data item. 300
Group Assigns tags. Up to 32 tags can be assigned to a group. 50
Logical Configuration Diagram
TAG001
GateMODBUS
TAG002
TAG003
TAG004
TAG200
Tag
Assignments
Group
Group
Acquisition Conditions
The following items are included in the acquisition conditions.
Data scan interval (0.5–3600 sec)
For information on the data acquisition operation, see page 3-6, “Acquiring Data at
Fixed Intervals.”
Timeout time (1–10 sec)
Retry Use (ON/OFF).
Retry Interval (30–3600 sec.)
Tag
A tag is a name for a data value. You can use up to 100 tags with GateMODBUS. Data
obtained from the Modbus registers is assigned to each tag. The following items are
included in tag settings.
Used serial ports (COM1–COM9) and Ethernet ports (Ether1 to Ether16)
The read Modbus function (03 or 04)
Register numbers read
For Modbus function 03: 40001–49999, 400001–465535
For Modbus function 04: 30001–39999, 300001–365535
Data Type
See page 3-8, “Data Type.”
Scaling variable
See page 3-10, “Data Scaling.”
Decimal place
Upper/lower span value
Tag name
Unit
3.2 Detailed Description of Functions