Owner's manual

3-3
IM WX1-05E
1
2
3
Index
Detailed Description Functions
3.2 Detailed Description of Functions
Communication Port
The communications ports available to GateMODBUS are the COM1–COM9 serial
(RS-232) ports the Ether1 to Ether16 Ethernet ports. The following items are specified in
the Serial Setting tab.
Serial port setting
Baud rate (4800, 9600, 19200, or 38400 bps)
Parity (None, Even, or Odd)
Ethernet port setting
IP address or host name
Password
Note
The Modbus protocol’s RTU (remote terminal unit) mode prescribes stop bit 2 for no parity, and
stop bit 1 for odd or even parity.
Modbus Communications
GateMODBUS supports communications using the Modbus/RTU (serial) and Modbus/
TCP (Ethernet) protocols. The functions and registers used by GateMODBUS for data
logging are as follows:
Function 03 04
Description Read holding register Read input register
Register numbers that can be loaded: 40001–49999 400001–465535
30001–39999 300001–365535
Also, you can execute the following functions on the configurator to display the
connection status with Modbus devices.
Function 08
Sub-function 00
Description Loop back test
Note
GateMODBUS does not support the Modbus protocol’s Modbus/ASCII mode.