Owner's manual
2-4
IM WX1-05E
Tag Settings
Procedure
1.
Click the Tag Setting tab or choose View > Tag setting from the menu bar.
Drag to select a range of items (up to 300 channels can be selected)
Turns all selected
items ON/OFF
Click to display a list
Register numbers are filled from the first cell in the selection
to the last, each line being given a register number 1
Select/deselect all items
Click to turn a single item ON/OFF
Copies the setting in
the first item of the
selection to all of the
items in the selection
2.
Enter the following settings.
Tag number: ON (blue)/OFF (gray)
Port: NONE, COM1–COM9, Ether1–Ether16
Modbus address: Enter the address for the Modbus device.
Modbus function: 03 or 04
Modbus register numbers:
For Modbus function 03, 40001-49999, 400001-465535
For Modbus function 04, 30001-39999, 300001-365535
Modbus data type: Depends on the Modbus device header. (See page
3-8, “Data Type”)
Scaling coefficient: (See page 3-10, “Data Scaling”)
Scaling offset:
(See page 3-10, “Data Scaling”)
Decimal position: An integer from 0–4
Span Lower/Upper: Setting range varies depending on the decimal
position. (See page 3-5, “Upper/Lower Limit of Span”)
Unit: Enter up to 6 alphanumeric chara
cters.
Tag name: Enter up to 16 alphanumeric characters.
2.2 Entering Environment Settings