Instruction Manual
4-44
IM WX102-01E
4.21  Setting Relay and Internal Switch Actions
Open the Alarm Setup setting screen for Relay and Internal Switch Actions as follows:
Click the SETUP tab and select Relay from the SETUP (Basic) Setting contents box, or 
select from the menubar Settings > SETUP (Basic) Settings > Relay > and the desired 
relay setting.
Select a SETUP topic SETUP tab
Relay AND/ORReflashing Alarm
Relay hold
Relay (De-)
Energizing
Reflashing Alarm Setting
When several alarms share the same alarm output relay, you can select this setting 
which results in a short de-operation of the relay when a second alarm occurs.
Relay AND/OR 
Select how the internal switches/alarm output relays will be operated, when a group of 
alarms share the same internal switch or alarm output relay.
AND :   will be operated when all alarms are occurring;
OR : 
 will be operated when at least one alarm is occurring.
Use the pull-down menu to select AND settings in a range starting from relay 1, or 
choose NONE for all OR actions.
Relay (De-)Energizing 
Select alarm output relays to be energized or de-energized on alarm occurrence. A blue 
circle in the (De-)Energizing dialog box marks the active setting. 
Copy Relay (De-)Energizing settings by clicking the number of the settings you want 
to copy to other channels. The display color changes. Click the copy button in lower 
left corner of the setting screen. Click the first channel you want to copy the settings to, 
and drag the mouse pointer down to the last channel the settings should be copied to. 
The display color of the selected channels changes. Click the Paste button, to copy the 
selected settings to the selected channels.
Relay Hold Setting
Select whether to Hold, or Not Hold, the operating status of operated internal switches 
or alarm output relays. This setting applies to both the internal switches and the alarm 
output relays.
DO External Relay Setting (DA100 only)
For DA!00 you may also use the Command DO to set Relays externally (with a PC) ON 
or OFF. The relay is set from the Base unit to each complete module. If the relays set 
here are alarm output relays, then normal alarm output relays in the same will be set 
OFF.