Owner's manual
8-29
IM WX104-01E
1
2
3
4
5
6
7
8
9
Index
Configuring the CX1000/CX2000
Partial
Expand(%)
The boundary value is displayed as a percentage along the width of the display, between 
1 and 99%.
Boundary
The setting conditions depend on the internal control channel and external control 
channel as follows:
•  Internal contorol channel
  PV/SP: EU (0%) < boundary value < EU (100%)
  OUT:
  EU (–5.0%) < boundary value < EU (105.0%)
  However, for retransmission OUT, minimum span value < boundary value < maximum 
span value
•  External contorol channel
  span L < boundary value < span U
  However, when external loop is of
f, the partial expansion/reduction is also off.
Note
•  The partial expansion/reduction settings are valid when [Partial] is set to [Use] in [Aux] of the 
[Setup] tab.
•  For the external control channel, set a boundary within the span determined by the internal 
span -50–1050 and the specified decimal point. Normally there is one decimal place, so it 
can be set to -5.0% < boundary < 105.0%.
Color
For each channel you can choose from 16 colors.
8.5 Control Channel Settings (Internal/External)