Owner's manual
7-48
IM WX104-01E
Command setting
•  Client command No.
  Select from 1 to 16 for the transmitted command numbers to be congured.
•  Command
  Set the command type.
Settings Description
Read Read to the external input channel (16-bit signed integer type) from the server.
R-Math Read to the communication input data (32-bit floating point type) from the server.
Write Write the measurement channel (16-bit signed integer type) to the server.
W-Math Write the measurement channel (32-bit signed integer type) to the server.
  [Read] can be selected on MV2000s with the external input channel (/
MC1 option) installed.
  [R-Math] and [W-Mat] can be selected on models with the computation function (/M1 option) 
installed.
•  Start channel/End channel (client channels)
  Enter the rst and last channel numbers of input/output. The range of channels that 
you can enter varies depending on the command type as follows:
  Read: 201 to 440, R-Math: C01 to C60, Write: 1 to 48, W-Math: 101 to 160
•  Connected to (server number)
  Select the server number from 1 to 16.
•  Register
  Set the register number of the server.
  For an input register, select in the range of 30001 to 39999 and 300001 to 365536. 
For a hold register, select in the range of 40001 to 49999 and 400001 to 465536.
  The register numbers you can specify vary depending on the command type. See 
section 6/3 of the MV1000/MV2000 Communication Interface User’
s Manual (IM 
MV1000-17E). 
•  Type
  Select INT16, UINT16, INT32_B, INT32_L, UINT32_B, UINT32_L, FLOAT_B, or 
FLOAT_L.
  The register numbers you can specify vary depending on the command type. See 
section 6.3 of the MV1000/MV2000 Communication Interface User’
s Manual (IM 
MV1000-17E). 
7.5 Entering Basic Settings