Owner's manual
2-9
IM WX11-01E
Creating Monitor Screens with AddObserver Builder
1
2
3
4
Index
13.
 To manually input the tag and color settings, click   in the Att. column. The 
arrow changes to 
, and the tag and color settings can be entered.
    •  Tag and Tag Comment
  Enter the tag name or tag comment.
  Tag numbers of up to eitht characters can be input.
  Tag comments of up to 32 characters can be input. 
    •  Format
  Enter the format type and decimal place. Click the icon on the left to toggle 
between 
 and  .   is a xed-point representation, and   is a oating-
point representation. The value on the right determines how many places past 
the decimal point are shown. Up to 6 places can be selected.
    •  Minimum/Maximum/Units
  Enter the maximum value, minimum value, and units for the span.
    •  Color
  Enter the colors for the trend graph and zone bar.
Note
Be aware that If you switch back to   after entering user settings, all previously entered 
settings will be lost.
Adding a Channel
14.
 Click the Insert button. A new channel is added to the bottom of the list.
Deleting a Channel
14.
 Select the channel you wish to delete, and click the Delete button.
Deleting Unused Channels
14.
 Select a range of channels. Click the Del Unused button. All unused channels in 
the selected range will be deleted.
Copying a Channel
14.
 Select the channel or channels you wish to copy and click the Copy button. Then 
select the channel onto which you wish to paste the copied channel, and click 
the Paste button. The setting information from the copied channel appears in the 
selected channel.
Loading the Default Values
14.
 Select the range of channels into which you wish to load the default values. 
Click the Default button. The settings for all channels in the selected range are 
changed to their default values.
Inset
Delete
Copy
Paste
Default
Del Unused
2.4 Entering Host and Channel Settings