Owner manual

3-6
IM WX1-07E
Processing Alarm Statuses
Each model’s alarm types are changed as follows before being sent to DAQLOGGER
and Remote Monitor.
Alarm Type on Device Side Alarm Type after Change
PV SP OUT, HOUT, COUT
PV high limit PV high limit [H]
PV low limit PV low limit [L]
Deviation high limit Deviation high limit [DH]
Deviation how limit Deviation low limit [DL]
De-energized on deviation high limit
alarm
Deviation high limit [DH]
De-energized on deviation low limit
alarm
Deviation low limit [DL]
Deviation high and low limit Other [ETC]
Deviation within high and low limit Other [ETC]
De-energized on PV high limit PV high limit [H]
De-energized on PV low limit PV low limit [L]
PV high limit
(with idle mode)
PV high limit [H]
PV low limit
(with idle mode)
PV low limit [L]
Deviation high limit
(with idle mode)
Deviation high limit [DH]
Deviation low limit (with idle mode) Deviation low limit [DL]
De-energize on deviation high limit
alarm (with idle mode)
Deviation high limit [DH]
De-energize on deviation low limit alarm
(with idle mode)
Deviation low limit [DL]
Deviation high and low limit
(with idle mode)
Other [ETC]
Deviation within high and low limit
(with idle mode)
Other [ETC]
De-energized on PV high limit
(with idle mode)
PV high limit [H]
De-energized on PV low limit
(with idle mode)
PV low limit [L]
Timer function upward (hour/minute) Other [ETC]
Timer function downward (hour/minute) Other [ETC]
Timer function upward (minute/second) Other [ETC]
Timer function downward
(minute/second)
Other [ETC]
Sensor grounding alarm Other [ETC]
Fault diagnosis output Other [ETC]
FAIL output Other [ETC]
Timer function Other [ETC]
De-energized on timer function Other [ETC]
Heater burnout alarm 1 Other [ETC]
Heater burnout alarm 2 Other [ETC]
Heater burnout Other [ETC]
SP high limit Other [ETC] SP high limit [H]
SP low limit Other [ETC] SP low limit [L]
Output high limit Other [ETC] Output high limit [H]
Output low limit Other [ETC] Output low limit [L]
PV velocity alarm Other [ETC]
PV velocity alarm passive Other [ETC]
Self-diagnostic alarm Other [ETC]
Self-diagnostic alarm passive Other [ETC]
FAIL passive Other [ETC]
Deviation high limit for target setpoint Other [ETC] Deviation high limit [DH]
Deviation low limit for target setpoint Other [ETC] Deviation low limit [DL]
(cont. on next page)
3.3 Details on Functions