ConguringtheRD-MV1000Client(Modbusclient)
The description below assumes that settings other than destination server settings and
commands are at default values.
RegisteringtheDestinationServer
The example below describes the settings used to register the RD-MV1000 server to
number 1.
The RD-MV1000 server IP address is assumed to be 192.168.1.101.
◊ Press MENU and then select Menu tab > Basicsettingmode > Menu tab >
Communication(Ethernet) > Modbusclient > Modbusserversettings
Parameter Setting
Port 502
Modbus server name 192.168.1.101
Unit Auto
SettingTransmissionCommands
◊ Press MENU and then select Menu tab > Basicsettingmode > Menu tab >
Communication(Ethernet) > Modbusclient > Commandsettings
Parameter Setting
Command type R-M
First and Last C01
Server 1
Regi. 30001
Type INT16
2.10UsageExampleoftheModbusFunction