Owner manual

1-36
IM MV1000-01E
1.7 Event Action Function
The event action function performs a specified action when a specified event occurs. The
remote control function (/R1 option) is configured using the event action function.
For configuration instructions, see section 7.1.
Event
List of Events
You can choose from the following events:
Event Level/edge* Description
Remote Level/edge Remote control input ON or OFF.
Relay Level/edge Alarm output relay activation or deactivation.
Switch Level/edge The internal switch value (0 or 1).
Timer Edge Timer timeout
MatchTimeTimer Edge When a specified time is reached.
Alarm Level/edge An alarm is occurring/no alarms are occurring
UserKey Edge When the USER key is pressed.
* For a description of level and edge, see “Miscellaneous” in this section.
Timers
There are four kinds of timers. They are also used with the TLOG computation
function (/M1 and /PM1 options).
Types of Timers
Time
Relative timerAbsolute timer
Timer set
Timer reset
B: Interval
Timeout
Time
Timer set
Ref. time
A: Interval
A BBA A A
Absolute Time Mode
The timer expires at the times determined by the reference time and the interval.
The reference time can be set to the hour (00 to 23).
Example:
Reference time: 00:00
Interval: 10 min
The timer expires at 00:00, 00:10, 00:20, ... 23:40, and 23:50. For
example, if the timer is set at 09:36, the timer expires at 09:40, 09:50,
10:00, and so on.
Relative Time Mode
Timing begins when the timer is set, and the timer expires and then begins timing
again at each interval. With this mode, the timer will stop when there is a power
failure and will not resume afterwards.
Example: Interval:
00:15
The timer expires every 15 minutes.