File Output Example
Below is an example of manually sampled data for channels 1, 2, 3, and 4.
YREC
Manual Sample Data Version 1.00.00
Model MV2000
Language Code
shift-JIS
File Status Progress
Serial No. S5E701600
File Header
Ch CH001 CH002 CH003 CH004
Tag TI-101 OUT-102 FI-103 VA-204
Unit ˚C V m3/h %
2008/01/23 08:57:22 213.8 0.517 368.4 68.9
2008/01/23 08:57:28 208.6 0.494 363.0 68.1
Note
• The output when error data, range-out data, or computation range-out data is detected
Channel Data Output
Measurement
channels and
Error (Space)
external input
channels
Positive range-out (includes burnout detection) 99999
Negative range-out (includes burnout detection) –99999
Computation
channels
Error 999999999
Positive computation range-out (when the value
exceeds approx. 3.4E+38)
999999999
Negative computation range-out (when the value is
less than approx. –3.4E+38)
–999999999
•
The MV generates a new manually sampled data file in the following cases:
•
A measurement channel is changed to Skip from a range other than Skip.
• A measurement channel is changed from Skip to a range other than Skip.
• A computation or external input channel is changed from On to Off or Off to On.
• The unit is changed.