About TimerReset
If Event is set to Relay, Switch, MatchTimeTimer, or Alarm, TimerReset will not result
in a timeout (an action will not be executed even if the timer is used as an event).
If Event is set to Remote or UserKey, a timeout will occur (if the timer is used as an
event, an action will be executed).
About PanelLoad
PanelLoad can only be specied as an action when Event is set to Remote.
PanelLoad loads a setup data le, LOAD1.PDL, LOAD2.PDL, or LOAD3.PDL, in
the root directory of the CF card onto the MV, and uses it to congure the MV. Only
settings that pertain to Setting Mode are updated.
You must create a setup le and save it to the CF card in advance.
Event Trigger Operation
When Event is set to Relay, Switch, or Alarm:
The Trigger action will always occur when an output relay is activated, when an
internal switch is set to 1, or when an alarm occurs. However, the number of times the
trigger is activated depends on the event data mode (Single or Repeat).
About TimeAdjust
TimeAdjust can only be specied as an action when Event is set to Remote.
TimeAdjust sets the MV internal clock to the closest hour.
• OperationWhentheMVisNotMemorySampling
Difference from the Nearest Hour Operation
0 s to 1 min 59 s Truncates the minutes and seconds.
Example: 10 hours 01 min 50 s becomes 10 hours 00
min 00 s.
2 min to 57 min 59 s The time is not changed.
58 min to 59 min 59 s Rounds up the minutes and seconds.
Example: 10 hours 59 min 50 s becomes 11 hours 00
min 00 s.
• OperationWhentheMVisMemorySampling(Seesection1.11for
details.)
If the time difference between the time when the remote control signal is applied
and the nearest hour is within the preset time, the time is gradually corrected.
Otherwise, the time is corrected immediately.
1.7 Event Action Function