3.5 Reading/Writing Data on Another Device from
the MV via Modbus
The MV is a Modbus master.
For Modbus specifications, see section 7.3.
Conguring the Serial Interface
Set Protocol to Master-M under Serial basic settings. See section 3.3 for details.
Conguring the Modbus Master
Press MENU and then select Menu tab > Basic setting mode > Menu tab >
Communication (Serial) > Modbus master > Basic settings or Command settings
Basic settings
Command Settings
Basic Settings
Read cycle
Set the read cycle to 125ms, 250ms, 500ms, 1s, 2s, 5s, or 10s.
timeout
Set the command timeout value to 125ms, 250ms, 500ms, 1s, 2s, 5s, 10s, or 1min.
The timeout value is the maximum amount of time the MV waits for a response from
the specified slave after the MV sends a command.
Retrials
Set the number of retrials when there is no response from the slave. Select Off, 1, 2, 3,
4, 5, 10, or 20.
Inter-block delay
Set the amount of time the MV waits after receiving a response to send the next
command. Set the amount of time to Off, 5 ms, 10 ms, 15 ms, 45 ms, or 100 ms.
Auto recovery
Set the auto recovery time from communication halt. Select Off, 1min, 2min, 5min,
10min, 20min, 30min, or 1h.
Command Settings
Master command number
Select 1-8 or 9-16 for the command numbers to be configured.
Command type
Set the transmission command type to Off, R, R-M, W, or W-M.
R: Read the data from the slave into external input channels (16-bit signed
integer)
R-M: Read the data from the slave into communication input channels (32-bit
floating point)
W:
Write computation channel data (16-bit signed integer) to the slave
W
-M: Write computation channel data (32-bit signed integer) to the slave
R
is selectable on the MV2000 when external input channels (/MC1 option) is installed.
R-M
and
W-M
are selectable when the computation function (/M1 or /PM1 option) is
installed.