Manual
4-27
Commands
IM MV1000-17E
1
2
3
4
5
6
7
App
Index
Description You can execute this command on models with
the /MC1 external input channel option.
EM Starts/stops the e-mail
transmission function
Syntax
EM p1<terminator>
p1
Operation type
0
Start
1
Stop
Example
Start the e-mail transmission function.
EM0
Description T
o use the e-mail transmission function,
you must set the Ethernet interface, e-mail
addresses, and contents to be transmitted.
CU Manually recovers Modbus
Syntax
CU p1<terminator>
p1
Communication type
0
Modbus client (Ethernet)
1
Modbus master (serial)
BV Enters characters
Syntax
BV p1,p2<terminator>
p1
0
p2
Character string (up to 100 characters)
Example
Enter user123.
BV0,user123
KE Key operation command
Syntax
KE p1<terminator>
p1
Key type
F1
–
F7
Soft keys 1 to 7
ESC
ESC key
MENU
MENU key
FUNC
FUNC key
START
START/STOP key
HISTORY
HISTORY key
USER
USER key
T/DIV
T/DIV key
0
–
9
Number 0 to 9 keys
MINUS
Number minus key
DOT
Number decimal key
DISP
DISP/ENTER key
UP
Up arrow key
DOWN
Down arrow key
RIGHT
Right arrow key
LEFT
Left arrow key
Example Press the DISP/ENTER key.
KEDISP
Description Operates in the same way as the keys on the
MV. For a key sequence, transmit the commands
in the same order that you would press the keys
on the MV.
YC Clears measured/computed data
and initializes setup data
Syntax
YC p1<terminator>
p1
T
ype of data to be cleared
0
Clear measured/computed data
and initialize setup data
2
Clear measured/computed data
IR Resets the relative timer
Syntax
IR p1<terminator>
p1
T
imer number to be reset
0
All timers
1
–
4
Timer number 1 to 4
MA Resets a match timer
Syntax
MA p1
P1
Match timer number to be reset (1 to 4)
Example
Reset match timer number 3.
MA3
Description •
An error will occur if the timer operation of the
match timer is set to repeat.
•
Nothing will occur
if the single match timer has
not expired.
NR Sets the trend interval
Syntax
NR p1,p2<terminator>
p1
1
p2
T
rend interval [/div] (15S, 30S, 1MIN, 2MIN,
5MIN, 10MIN, 15MIN, 20MIN, 30MIN, 1H,
2H, 4H, 10H)
Query
NR[ p1[,p2]]?
Example
Set the trend interval to 5 min/division.
NR1,5MIN
Description
•
Y
o
u
cannot set the trend interval if the memory
data type is event + display.
•
The logging number is fixed to 1.
•
Set the trend/strage interval and auto-save
interval first with the SW command and then
set the trend interval with the NR command.
4.5 Setting Commands (Control)