Owner manual

Ext. channel > Alarm mark, Color scale band
Setting Selectable Range or Choices Default Value
First-CH, Last-CH Numeric value (external input channel number)
201 to 440
201
Alarm mark Mark kind Alarm/Fixed Alarm
Indicate on Scale
On/Off Off
Alarm mark color > Alarm 1 to 4
Red, Green Blue, B.violet, Brown, Orange,
Y.green, Lightblue, Violet, Gray, Lime, Cyan,
Darkblue, Yellow, Lightgray, Purple, Black, Pink,
L.brown, L.green, Darkgray, Olive, DarkCyan,
S.green
Alarm 1: Red
Alarm 2: Orange
Alarm 3: Orange
Alarm 4: Red
Color scale
band
Band area Off/In/Out Off
Color Red, Green Blue, B.violet, Brown, Orange,
Y.green, Lightblue, Violet, Gray, Lime, Cyan,
Darkblue, Yellow, Lightgray, Purple, Black, Pink,
L.brown, L.green, Darkgray, Olive, DarkCyan,
S.green
Lime
Display position >
Lower
Numeric value (measurement range) 0.00
Display position >
Upper
Numeric value (measurement range) 1.00
Data save > File settings
Setting Selectable Range or Choices Default Value
Disp/Event File > File format Binary/Text Binary
File header > Characters Character string (up to 50 characters)
Data file name Structure Date/Serial/Batch Date
Identified strings Character string (up to 16 characters)
Data save > Save directory
Setting Selectable Range or Choices Default Value
Save directory > Directory name Character string (up to 20 characters) DATA0
Data save > Save directory
Setting Selectable Range or Choices Default Value
Disp data Trend/Storage interval 5s/10s/15s/30s/1min/2min/5min/10min/15min/
20min/30min/1h/2h/4h/10h (/div)
1min
Save interval 10min/20min/30min/1h/2h/3h/4h/6h/8h/12h/1day/
2day/3day/5day/7day/10day/14day/31day
1h
Data save > Event data
Setting Selectable Range or Choices Default Value
Event data Sample rate 25ms/125ms/250ms/500ms/1s/2s/5s/10s/30s/
1min/2min/5min/10min(varies depending on the
model)
1s
Mode Free/Single/Repeat Free
Data length 10min/20min/30min/1h/2h/3h/4h/6h/8h/12h/1day/
2day/3day/5day/7day/10day/14day/31day
1h
Pre-trigger 0/5/25/50/75/95/100 % 0
Trigger signal > Key On/Off On
Data save > Manual sample
Setting Selectable Range or Choices Default Value
Manual Sample number Numeric value (channel number)001 to 120 001
Manual Sample On/Off On/Off On
Channel 001 to 048, 101 to 160, 201 to 440 001
Default MV2000 Settings
43
IM MV2000-02E