Owner manual
Meas channel > Alarm mark, Color scale band
Setting Selectable Range or Choices Default Value
First-CH, Last-CH Numeric value (channel number) 1 to 48 001
Alarm mark
Mark kind Alarm/Fixed Alarm
Indicate on
Scale
On/Off Off
Alarm mark
color > Alarm 1
to 4
Red, Green Blue, B.violet, Brown, Orange, Y.green,
Lightblue, Violet, Gray, Lime, Cyan, Darkblue, Yellow,
Lightgray, Purple, Black, Pink, L.brown, L.green,
Darkgray, Olive, DarkCyan, S.green
Alarm 1: Red
Alarm 2: Orange
Alarm 3: Orange
Alarm 4: Red
Color scale
band
Band area Off/In/Out Off
Color Same as the mark color Lime
Display position
> Lower
Numeric value (measurement range) 0.0000
Display position
> Upper
Numeric value (measurement range) 0.0100
Meas channel > Calibration correction
Setting Selectable Range or Choices Default Value
First-CH, Last-CH Numeric value (channel number) 1 to 48 001
Calibration
correction
Number of set
points
Off/2/3/4/5/6/7/8/9/10/11/12/13/14/15/16 Off
Mes val Input/Measure –2.0000
True val Numeric value (measurement range) –2.0000
Meas channel > Calculation expression, Alarm
Setting Selectable Range or Choices Default Value
First-CH, Last-CH Numeric value (computation channel number) 101 to 160 101
Math range Math On/Off On/Off Off
Calculation
expression
Character string (up to 120 characters) –
Span Lower Numeric value (–9999999 to 99999999, decimal place 0
to 4)
–200.00
Span Upper Numeric value (–9999999 to 99999999, decimal place 0
to 4)
200.00
Unit Character string (up to 6 characters) —
Alarm 1 to 4 On/Off Off
Type H/L/T/t H
Value Numeric value 0.00
Relay On/Off On/Off Off
Number I01 to I06/I11 to I16/S01 to S30 I01
Detect On/Off On
Math channel > Constant
Setting Selectable Range or Choices Default Value
Number of constant K01–K60 K01
Constant > Value Numeric value (–
9.9999E+29 to –1.0000E–30,
0,
1.0000E–30 to –9.9999E+29)
1
Math channel > Tag, Memory sample, Alarm delay
Setting Selectable Range or Choices Default Value
First-CH, Last-CH Numeric value (computation channel number) 101 to 160 101
Tag > Characters Character string (up to 16 characters) —
Memory sample > On/Off On/Off On
Alarm delay > Time Numeric value (1 to 3600) s 10
Default MV2000 Settings
40
IM MV2000-02E