Owner manual
Setting Mode Settings and Default Values
Menu Tab
Meas channel > Range, Alarm
Setting Selectable Range or Choices Default Value
First-CH, Last-CH Numeric value (channel number) 1 to 48 001
Range>Mode Skip/Volt/TC/RTD/Scale/Delta/DI/1-5V/Sqrt Volt
Mode=Volt
Range 20mV/60mV/200mV/2V/6V/20V/50V 2V
Span Lower Numeric value (depends on the range) –2.0000
Span Upper Numeric value (depends on the range) 2.0000
Mode=TC
Range R/S/B/K/E/J/T/N/W/L/U/WRe R
Span Lower Numeric value (depends on the range) 0.0
Span Upper Numeric value (depends on the range) 1760.0
Mode=RTD
Range Pt/JPt Pt
Span Lower Numeric value (depends on the range) –200.0
Span Upper Numeric value (depends on the range) 600.0
Mode=Scale
Type Volt/TC/RTD/DI Volt
Range 20mV/60mV/200mV/2V/6V/20V/50V (type = Volt)
R/S/B/K/E/J/T/N/W/L/U/WRe (type = TC)
Pt/JPt (type = RTD)
Level/Cont (type = DI)
2V
R
Pt
Level
Span Lower Numeric value (depends on the range) –2.0000
Span Upper Numeric value (depends on the range) 2.0000
Scale Lower Numeric value (depends on the range) 0.00
Scale Upper Numeric value (depends on the range) 200.00
Unit Character string (up to 6 characters) —
Mode=Delta
Type Volt/TC/RTD/DI Volt
Range 20mV/60mV/200mV/2V/6V/20V/50V (type = Volt)
R/S/B/K/E/J/T/N/W/L/U/WRe (type = TC)
Pt/JPt (type = RTD)
Level/Cont (type = DI)
2V
R
Pt
Level
Span Lower Numeric value (depends on the range) –2.0000
Span Upper Numeric value (depends on the range) 2.0000
Ref. CH Numeric value (measurement channel number) 001
Mode=DI
Range Level/Cont Level
Span Lower Numeric value (0, 1) 0
Span Upper Numeric value (0, 1) 1
Mode=1-5V
Range 1-5V 1-5V
Span Lower Numeric value (0.800 to 5.200) 1.000
Span Upper Numeric value (0.800 to 5.200) 5.000
Scale Lower Numeric value (–30000 to 30000, decimal place 0 to 4) 0.00
Scale Upper Numeric value (–30000 to 30000, decimal place 0 to 4) 200.00
Unit Character string (up to 6 characters) —
Low-cut On/Off Off
Mode=Sqrt
Range 20mV/60mV/200mV/2V/6V/20V/50V 2V
Span Lower Numeric value (depends on the range) –2.0000
Span Upper Numeric value (depends on the range) 2.0000
Scale Lower Numeric value (–30000 to 30000, decimal place 0 to 4) 0.00
Scale Upper Numeric value (–30000 to 30000, decimal place 0 to 4) 200.00
Unit Character string (up to 6 characters) —
Low-cut On/Off Off
Low-cut value 0.0 to 5.0 (%) 0.5
Default MV2000 Settings
38
IM MV2000-02E