Manual

Communication (Ethernet) > Modbus client > Modbus server settings
Setting Selectable Range or Choices Default Value
Server number 1-8/9-16 1-8
Port Numeric value (0 to 65535) 502
Modbus server name Character string (up to 64 characters)
Unit Auto/Fixed Auto
No. 0 to 255 1
Communication (Ethernet) > Modbus client > Command settings
Setting Selectable Range or Choices Default Value
Master command number 1-8/9-16 1-8
1 to 16 Off/R-M/W/W-M Off
First Varies depending on the send command type
Last Varies depending on the send command type
Server 1/2/3/…/15/16 1
Regi. Numeric value (register number)
R-M:30001
W, W-M: 40001
Type INT16/UINT16/INT32_B/INT32_L/UINT32_B/
R-M, W: INT16
UINT32_L/FLOAT_B/FLOAT_L
W-M: INT32_B
Communication (Serial) > Basic settings
Setting Selectable Range or Choices Default Value
Serial
Baud rate 1200/2400/4800/9600/19200/38400 9600
Data length 7/8 8
Parity Odd/Even/None Even
Handshaking Off:Off/XON:XON/XON:RS/CS:RS Off:Off
Address Numeric value (1 to 99) 1
Protocol Normal/Modbus/Modbus-M Normal
Communication (Serial) > Modbus master > Basic settings
Setting Selectable Range or Choices Default Value
Modbus master basic settings
Read cycle 125ms/250ms/500ms/1s/2s/5s/10s 1s
Timeout 125ms/250ms/500ms/1s/2s/5s/10s/1min 1s
Retrials Off/1/2/3/4/5/10/20 1
Inter-block delay Off/5ms/10ms/15ms/45ms/100ms Off
Auto recovery Off/1min/2min/5min/10min/20min/30min/1h 2min
Communication (Serial) > Modbus master > Command settings
Setting Selectable Range or Choices Default Value
Master command number 1-8/9-16 1-8
1 to 16 Off/R-M/W/W-M Off
First Varies depending on the send command
Last Varies depending on the send command
Addr. Numeric value (1 to 247) 1
Regi. Numeric value (register number)
R-M: 30001
W, W-M: 40001
Type INT16/UINT16/INT32_B/INT32_L/UINT32_B/
R-M, W: INT16
UINT32_L/FLOAT_B/FLOAT_L
W-M: INT32_B
Default MV1000 Settings
56
IM MV1000-02E