Manual

Setting Mode Settings and Default Values
Menu Tab
Meas channel > Range, Alarm
Setting Selectable Range or Choices Default Value
First-CH, Last-CH Numeric value (channel number) 1 to 24 1
Range > Mode Skip/Volt/TC/RTD/Scale/Delta/DI/1-5V/Sqrt Volt
Volt
Range 20mV/60mV/200mV/2V/6V/20V/50V 2V
Span_L Numeric value (depends on the range) –2.0000
Span_U Numeric value (depends on the range) 2.0000
TC
Range R/S/B/K/E/J/T/N/W/L/U/WRe R
Span_L Numeric value (depends on the range) 0.0
Span_U Numeric value (depends on the range) 1760.0
RTD
Range Pt/JPt Pt
Span_L Numeric value (depends on the range) –200.0
Span_U Numeric value (depends on the range) 600.0
Scale
Type Volt/TC/RTD/DI Volt
Range 20mV/60mV/200mV/2V/6V/20V/50V (type = Volt)
R/S/B/K/E/J/T/N/W/L/U/WRe (type = TC)
Pt/JPt (type = RTD)
Level/Cont (type = DI)
2V
R
Pt
Level
Span_L Numeric value (depends on the range) –2.0000
Span_U Numeric value (depends on the range) 2.0000
Scale_L Numeric value (depends on the range) 0.00
Scale_U Numeric value (depends on the range) 200.00
Unit Character string (up to 6 characters)
Mode = Delta
Type Volt/TC/RTD/DI Volt
Range 20mV/60mV/200mV/2V/6V/20V/50V (type = Volt)
R/S/B/K/E/J/T/N/W/L/U/WRe (type = TC)
Pt/JPt (type = RTD)
Level/Cont (type = DI)
2V
R
Pt
Level
Span_L Numeric value (depends on the range) –2.0000
Span_U Numeric value (depends on the range) 2.0000
Ref. CH Numeric value (measurement channel number) 001
Mode = DI
Range Level/Cont Level
Span_L Numeric value (0, 1) 0
Span_U Numeric value (0, 1) 1
Mode = 1-5V
Range 1-5V 1–5V
Span_L Numeric value (0.800 to 5.200) 1.000
Span_U Numeric value (0.800 to 5.200) 5.000
Scale_L Numeric value (–30000 to 30000, Decimal place 0 to 4) 0.00
Scale_U Numeric value (–30000 to 30000, Decimal place 0 to 4) 200.00
Unit Character string (up to 6 characters)
Low-cut On/Off Off
Mode = Sqrt
Range 20mV/60mV/200mV/2V/6V/20V/50V 2V
Span_L Numeric value (depends on the range) –2.0000
Span_U Numeric value (depends on the range) 2.0000
Scale_L Numeric value (–30000 to 30000, Decimal place 0 to 4) 0.00
Scale_U Numeric value (–30000 to 30000, Decimal place 0 to 4) 200.00
Unit Character string (up to 6 characters)
Low-cut On/Off Off
Value 0.0 to 5.5 % 0.5
Range > Alarm 1 to 4 On/Off Off
Default MV1000 Settings
39
IM MV1000-02E